KFFP 2x1.0mm2 High-Temperature Control Cable
Standard TICW/03-2009
Section 1: Illustration of High-Temperature Control Cable

High-Temperature Control Cable Applications
High-temperature control cables are used for control wiring of electrical equipment and appliances, with a long-term operating temperature of 200°C. The bend radius should not be less than 8 times the cable outer diameter, and cables with armor or shielding should have a bend radius not less than 15 times the cable outer diameter. Suitable for high-temperature environments in industrial and mining enterprises, energy and transportation departments, and for control and protection circuits operating at alternating current rated voltages of 450/750V or below.
Section 3: High-Temperature Control Cable Models and Composition

P1 Tin-plated wire shielding, P2 Copper strip shielding, P3 Aluminum/plastic composite film shielding, 9 Steel wire braided armor
For example:
Copper-core fluoroplastic insulated fluoroplastic sheathed copper wire screening control flexible cable, for mobile laying, rated voltage 450/750V, 19 cores, 1.5mm².
KFFRP-450/750V 19x1.5mm2
Copper-core Fluoroplastic Insulated Fluoroplastic Sheathed Control Cables, for Fixed Installation, Rated Voltage 450/750V, 7 cores, 1.5mm²
KFF-450/750V 7x1.5mm2
Section 4: High-Temperature Control Cable Specifications
Model | Conductor Nominal Cross-Sectionmm2 | ||||||
0.5 | 0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | |
Core Count | |||||||
KFF KFFP | - | 2-19 | 2-12 | ||||
KFFP2 | - | 2-19 | 2-12 | ||||
KFFR | 2-19 | 2-12 | |||||
KFFRP | 2-19 | 2-12 | |||||
KFF9F | - | 2-19 | 2-12 | ||||
Note: The recommended series of cores are:2, 3, 4, 5, 7, 8, 10, 12, 14, 16, 19 cores | |||||||
Section 5: Nominal Insulation Thickness of High-Temperature Control Cables
Conductor Nominal Section Area mm2 | Insulation Nominal Thicknessmm | Conductor Nominal Cross-Section mm2 | Insulation Nominal Thicknessmm | ||
450/750V | 0.6/1Kv | 450/750V | 0.6/1Kv | ||
0.5,0.75 | 0.30 | 0.35 | 2.5 | 0.35 | 0.40 |
1 | 0.30 | 0.35 | 4 | 0.45 | 0.50 |
1.5 | 0.30 | 0.40 | 6 | 0.45 | 0.50 |
Section 6: Nominal Thickness of High-Temperature Control Cable Sheath
Assumed outer diameter prior to packing sleeve compressiond mm | Nominal Thickness of the Jacket mm | Assumed Outer Diameter Prior to Squeezing Package Sheathd mm | Grommet Nominal Thickness mm |
d≤10 10<d≤16 | 0.6 0.7 | 16<d≤25 25<d≤30 | 0.9 1.1 |
Note: Control cables with large-diameter fluoroplastic insulated sheath are not considered at this time. | |||
Note:High-temperature control cable insulation sheath materials are all made of virgin material: polytetrafluoroethylene ethylene propylene (PFA, FEP, F46, Teflon, fluoro plastics, Teflon). The products feature resistance to high and low temperatures from -65°C to 200°C, -65°C to 260°C, oil resistance, corrosion resistance, acid and alkali resistance, and aging resistance.