DYJY 5KV D refers to the buried cable used for the runway assist lamp circuit
Other than that, it's a 6kV cross-linked polyethylene insulated and polyethylene sheathed dripless cable, just like conventional cables.
Aid Lighting Cable for Airport Runways Detailed Description
Airport Guidance Lighting Cable - Airport Guidance Lighting Cable: DJ-JJKR-0.6/1KV
Introduction to lighting cables for airport guidance lighting systems: DJ-JJKR-0.6/1KV low-voltage cable. This cable is used in airport power transmission systems, with a long-term operating temperature of ≤70°C. It features ethylene propylene insulation, a short-circuit temperature of ≤250°C for a duration of ≤5S, and an outer sheath made of flame-retardant PVC. The bend radius of the cable is greater than or equal to 15 times the cable's outer diameter.
2. DJ-JJKR-0.6/1KV for special locations, made with special materials.
(1) In case of tensile resistance, steel wire armor should be used. The effect of armor is to reduce the tensile force on the insulation and sheath during cable stretching, thereby protecting the core wire that shields the insulation and sheath.
(2) In areas with a subtropical climate or those with high acidity and alkalinity in the rain, it is advisable to add corrosion-resistant materials to the outer sheath to reduce the corrosion rate of the cable and enhance its service life.
Anhui Wanbang Special Cable Co., Ltd.
| Model Code | Code Description |
| D | Buried cable for airport runway lighting circuit |
| T | Copper conductor |
| YJ | Cross-linked polyethylene insulation |
| V | Polyvinyl Chloride (PVC) Sheath |
| Y | Polyethylene Sheath |
4.2 Product Model, Name, Specifications
| Model | Rated Voltage | Name | Specs |
| DYJY | 5kV | 5kV Copper Core Cross-Linked Polyethylene Insulated, Polyethylene Sheathed Burial Cable for Airport Auxiliary Lighting Circuit | 1X6 |
| DYJV | 5kV Copper Core Cross-Linked Polyethylene Insulated and Sheathed Cable for Airport Guidance Lighting Circuit, Suitable for Burial Installation |
5. Product cable reference parameters including outer diameter and weight
| Model | Specification mm2 | Conductor Outer Diameter mm | Insulation Nominal Thickness mm | Metal shielding thickness mm | Sleeve thickness mm | Cable Outer Diameter mm | Cable Reference Weight kg/km |
| DYJY-5kV | 1X6 | 3.1 | 2.8 | 0.07 | 1.40 | 15.9 | 252 |
| DYJV-5kV | 1X6 | 3.1 | 2.8 | 0.07 | 1.40 | 15.9 | 271 |
6. Key Technical Specifications
6.1 Conductivity Resistance:
The finished cable should have a conductor resistance not exceeding 3.08 Q/km at 20°C.
6.2 AC Voltage Test:
The finished cables have passed the 18kV/5min AC voltage test without any breakdown.
6.3 Partial Discharge Test
Finished cables should have a discharge amount not exceeding 10pC under 18kV test voltage.
7. Key Electrical Properties of Cables
| Test Items | Test Conditions | Technical Requirements |
| Conductor DC Resistance | 20℃ | ≤3.08Ω/km |
| AC Voltage Test | Apply alternating voltage of 18kV for 5 minutes | Cable insulation non-penetrable |
| Partial Discharge Test | Apply AC voltage of 18kV | (Standard Test) Discharge amount not exceeding 10pC Discharge quantity not exceeding 5pC (Type Test) |
| 4-hour AC voltage test | Apply alternating voltage of 20kV for 4 hours | Cable insulation non-penetrable |
| Insulation Resistance | 20℃ | ≥1500MΩ·km |
| 90℃ | ≥1.5MΩ·km |