DLH-105Flame DetectorPrimarily used for flame detection in gas industrial burners. The detection performance is reliable, capable of eliminating the effects of carbon accumulation and wiring distribution capacitance. It is sensitive only to flames and does not react to high-temperature radiation or convection, featuring strong anti-interference capability.

I. Main Technical Specifications

Power Voltage: 220V ±10%

2. Flame Detection - Ionization Electrode

3. Test response time ≤ 0.1 second

4. Electrode operating temperature; -60℃ - 1400℃; Long-term 1300℃

5. Test electrode to detector connection distance ≤ 100 meters

6. Flame Detector Dimensions: 85*65*65mm

Two: Pyromax high-temperature alloy detection electrodes

Diameter Φ8, extends into the fire zone Φ3.5

2. The installation of the flame detection electrode must be able to contact the flame, and it must be securely grounded. The detection hole is M14*1.25, with the electrode operating at a long-term temperature of 1300°C without the need for cooling.

3. Dimensions and length can be customized to customer's requirements.

Hot Line L for power connection

2. Neutral wire (N) for power connection

3. Contact Probe

4. Connect to the combustion unit or nozzle (grounded)

5. Normally closed contact of the first group of switches

6. Common terminal for the switch points of the first group

7. Connected to the normally open contact of the first group of switch points

8. Connected to the normally open contact of the second group of switches

9. Common terminal for the switch points of the second group

10. Connected to the normally closed contact of the second group of switches

IV. Installation

Electrode Installation

This detector employs a contact-based flame detection method. When installing the detection electrodes, ensure the central electrode can touch the flame during detection. The central electrode of the detection electrode must be insulated from ground and should not come into contact with any metal or refractory materials inside the burner. The housing of the detection electrode must be connected to the earth.

The central electrode material of the detection electrode is a special nickel alloy, which is resistant to high-temperature oxidation. No ventilation cooling is required during the installation of the detection electrode. The detection electrode can be used for a long time at a high temperature of up to 1300°C, with the operating temperature not exceeding 1400°C. Please select an appropriate location for installation.

2. Power Supply

If the user's communication power supply is an ungrounded source, such as supplied by an isolation transformer, please ground one wire of the power supply.


Disclaimer:Info provided by user, user liable for authenticity, accuracy & legality. Zhongshang114 assumes no liability.

Tip:Confirm supplier qualification & quality before purchase to avoid risks.

Unit Price Negotiable
Inquiry None
Delivery ShaanxiXi'an
Brand No content provided.
Categories High-energy igniter
Phone 151-2929-8995
Applicable Fuel Natural Gas
Expiry Long Valid
Update 2025-04-01 10:47
Gallery

Xi'an Zhengyu Thermal Energy Equipment Co., Ltd.Published byDLH-105 Ion Flame DetectorGallery Lib

Contact Merchant



Join

Successful Enterprise Join, Enjoy Multiple Privileges

Join Hotline:4006299930

Please scan with mobile phone

Customer Service

Service Hotline:4006299930

Official Account

WeChat Official Account, Get Business Opportunities

Scan to follow WeChat

Top