Low-voltage high-current transformer
Product Overview:
Low-voltage, high-current transformers, produced over the years with selected materials and advanced technology in our company, feature moisture resistance and easy maintenance. They can be deeply embedded in load centers and are suitable for power transmission and distribution in places like subways, high-rise buildings, airports, stations, ports, enterprises, and tunnels.
Low-voltage, high-current transformers, primarily used for AC power supply at 50-60Hz frequencies, with voltages not exceeding 700V, are suitable for various power supply locations, product input/output voltages, connection groups, and tap winding capacity distribution. These can all be carefully designed and manufactured according to customer requirements.
Terms of Use:
Operating Environment Temperature: -15~+50°C
Work Environment Humidity: 20~90%RH
Working atmosphere pressure: 860 hPa to 1060 hPa.
Storage/Transportation Temperature: -20°C to +55°C.
Key Technical Features:
Rated Capacity: 0.5kVA ~ 1000kVA
Input Voltage: Rated Voltage ±10%
Output Voltage: Rated Voltage ±5% (Load Tolerance)
Connection Method: △/Y (or other)
Frequency: ≥96%
Frequency: 50Hz/60Hz
Insulation Resistance: ≥50MΩ
Insulation Grade: H Class
Noise: ≤55dB (A-weighted)
Wen Sheng: ≤80K
Impedance Voltage Drop: ≤4%
Structure: Dry natural air-cooled
Interference Resistance Method: Double Shielded Grounding
Waveform Distortion: No additional waveform distortion.
Electrical Strength: No breakdown or flashover occurs under a 3000V sinusoidal voltage at power frequency for one minute.
Insulation Resistance (input/output to ground): Test voltage at least 1000VDC, insulation resistance greater than 2MΩ.
Function: Features input voltage, output voltage, and current indicators (this function requires cabinet configuration).
Protection: Features overcurrent protection (this function requires cabinet configuration to be enabled);
Overload Capacity: Twice the rated current for one minute.