Cable Tray Installation Requirements
1. The bottom of the bridge beam should not be less than 2.2m from the ground, the top should not be less than 0.3m from the floor, the distance from the beam should not be less than 0.05m, and the spacing between the bridge beam and power cables should not be less than 0.5m.
2. When bridge channels are parallel or intersect with various pipelines, their minimal clear distance should comply with the national standard "Code for Acceptance of Construction Quality of Electrical Installation Engineering" GB 50303—2002, specifically Article 12.2.1 and Table 12.2.1-2.
3. Fireproof seals should be installed in bridgeways and pipeline openings within vertical shafts and across different fire divisions.
4. Elbows, tees, and other fittings should be purchased as pre-fabricated products from bridge manufacturer, rather than being made on-site.

SuZhou ShunZeTong Electromechanical Installation Co., Ltd. was established in September 2013, located at No. 12 Datong Road, Suzhou High-tech Industrial Development Zone. Our company specializes in the installation of various pipelines and equipment. In recent years, we have assisted the environmental protection industry in completing over two hundred pollution treatment projects, including wastewater and waste gas treatment, as well as soil remediation. Our bridge installation services in Wujiang have received high praise from customers and led to long-term cooperative agreements. We also undertake the installation and long-term maintenance of pipelines, electrical systems, and equipment in various factories, and have become a long-term, high-quality supplier to several foreign enterprises. Our bridge installation projects have accumulated a strong customer base and earned us a good reputation.
Cable tray installation requirements and specification guidelines
Establish Direction: Based on the architectural floor plan, consider the layout of air conditioning and electrical piping, ease of maintenance, bridge installation costs, and cable routing density to determine the optimal route for cable trays. Indoors, install along the walls, columns, beams, and floors of the building as much as possible. If utilizing a utility tunnel, parallel installation should be considered on one side or above the pipes, and efforts should be made to avoid crossings of downlines and branch lines. If no other pipe racks are available, self-established (support) columns are required.

Suzhou Shunze Tong Electromechanical Installation Co., Ltd. was established in September 2013, located at No. 12 Datong Road, Suzhou High-tech Industrial Development Zone. Our company specializes in the installation of various pipelines and equipment. In recent years, we have assisted the environmental protection industry in completing over two hundred pollution control projects, including wastewater and air pollution treatment as well as soil restoration. We have received unanimous praise from our clients and have entered into long-term cooperative agreements with them.
Cable tray installation and construction process
Bridgeway installation
1. The bridge channel's right-angle bends, tees, and crosses should use the manufacturer's corresponding components; the construction unit should not make themself. The bridge channel cover plate should have no tilt, and the joints should be tight and neat.
2. Fire-resistant isolation measures should be taken when cable trays pass through fire walls and fire-rated floors.

Bridgeway Installation - Wujiang Bridgeway Installation - Shunzetong Electrical and Mechanical Installation Co., Ltd. 2, provided by Suzhou Shunzetong Electrical and Mechanical Installation Co., Ltd. Shunzetong Electrical and Mechanical has dedicated much enthusiasm and passion to the field of industrial maintenance and installation. We always prioritize our customers and aim to create value for them, winning the market with quality and service. We sincerely hope to cooperate with all sectors of society to achieve success and brilliance together. For related business inquiries, please contact Manager Ma.