Scope of Application
Primarily suitable for power lines in fire alarm and fire protection equipment, communication equipment, and emergency exit transportation systems that require fire resistance at rated voltages of 600/1000V and below. Particularly applicable to power transmission systems outside the containment of nuclear power plants under seismic loads, ensuring emergency shutdown, containment isolation, core emergency cooling, reactor heat removal, and prevention of radioactive material release into the surrounding environment.
Section 2: Product Model and Specifications
Section 3: Product Features
1. Excellent electrical and insulation properties.
2. Offers excellent heat aging resistance; long-term continuous working temperatures vary between 90℃ and 105℃ depending on the selected variety.
3. High load capacity, with strong overload protection performance.
4. Features halogen-free, low smoke, low toxicity, and environmental protection.
5. The cable has a low combustion transparency.
6. Excellent flame-retardant properties, passing the bundle combustion test.
7. Good fire resistance properties.
IV. Main Technical Performance
1. The finished cables operate at temperatures up to 90℃ and 105℃.
2. Finished cables meet the fire resistance test requirements of GB/T 19216.
3. The non-flammability of finished products is tested and passes the B-type bundle combustion test as specified in GB/T18380.3.
4. Cold resistance up to -40℃.
5. Insulation resistance constant Ki ≥ 3.67 MΩ·km
6. Conductor resistance meets the requirements specified in GB/T3956 for conductors.
7. Tested in accordance with GB/T17650 and GB/T17651
Tobacco Density Light Transmission ≥60%
pH Value ≥ 4.3
Conductivity ≤10μS/mm
V. Features
The conductor of the cable should not exceed a long-term working temperature of 90℃ or 105℃.
2. In the event of an accidental operating condition (duration not exceeding 5 seconds), the conductor's temperature should not exceed 270°C, and the laying temperature of the cable should be no less than 0°C.
3. Cable bend radius: Unarmored cables should not be less than 6 times the cable's outer diameter; armored cables should not be less than 12 times the cable's outer diameter.
4. The cable must not be subjected to mechanical impacts or sharp object cuts that could damage its performance before or after use.
Section 6: Delivery Length
1. Delivery length must be no less than 100 meters.
2. According to the agreement between both parties, delivery can be made in any length.
3. Length measurement error not exceeding ±0.5%.