Product Details
Fire Inspection Cabinet Product Overview:
Fire suppression water supply equipment is an essential component of the fire extinguishing system, and its performance and the adequacy of daily maintenance and management directly affect our safety and property. In recent years, the technology, performance, and level of automation of fire suppression water supply equipment have seen significant advancements. However, a common issue with various fire equipment is that upon receiving the start signal during a fire, the equipment fails to operate normally, delaying the fire extinguishing process. The primary reason for this is that fire pumps are often left unused and idle in their regular state. Additionally, due to the humid environment in the pump room, especially during summer, it is easy for moisture and rust to occur, leading to abnormal pump operation over time. Ultimately, this results in the fire pump failing to operate when a fire occurs, rendering it inoperable, and causing significant losses to the nation's property and the safety of the people. Therefore, our company, in accordance with national standards, GB16806-2006 "Fire Linkage Control System" Functional Requirements; self-developed and designedLSK-XFXJ Automatic Fire Pump Inspection and Control Equipment
Product Principle:
Shandong Lansheng Pump Industry producesAutomatic fire pump inspection and control equipment PLC programmable control technology, an intelligent control device for circulating inspection of fire pumps. In non-fire mode, the fire automatic inspection control device performs automatic inspection on the fire pumps. The automatic inspection cycle can be adjusted from a few hours to several hundred hours. The cycle clock automatically initiates the inspection program and also features manual inspection capability. During inspection, the inspection device checks the main circuit of the fire control cabinet and, upon confirming normalcy, drives each fire pump sequentially at a low speed. This operation has a low driving power, thus achieving energy-saving effects. If a fire operation signal is received during inspection, the automatic inspection device immediately interrupts the inspection, and the control device drives the fire pump into fire operation mode at power frequency. A new inspection process is only initiated after the next inspection cycle and without fire commands. During the inspection process, if a pump failure occurs, an alarm will be issued. The inspection device will also trigger an alarm in case of overvoltage, under-voltage, phase loss, phase error, overcurrent, or short circuit. This ensures that the pump does not suffer from rusting or being seized, and can operate normally during a fire.
Product Features
◇ Inspection Cycle: The inspection time can be set individually for each round, and the system can automatically determine if the fire pump can start normally.
The circulation inspection of fire pumps operates at low frequency and low speed. The inspection consumes minimal power, does not increase pressure in the water supply network, and does not exacerbate mechanical wear on the pump.
◇ Upon receiving fire command, the system will automatically shut down within 0.5 seconds and switch to the industrial frequency circuit. Ensuring the fire pump operates normally during a fire.
During automatic inspection, electrical components in the main circuit of the electrical control equipment can be tested to ensure the reliable operation of the electrical control equipment.
◇ The status and operation process of the pump are displayed on the LED and LCD, with a touch screen for setting and controlling its working state.
◇ Features fault storage function, with RS232, RS485 communication interfaces, capable of connecting to terminal computers for remote monitoring.
◇ Features expandable options, including circuit inspection, pipeline inspection, GPRS communication, printer and control, and summary communication modules.
◇ Equipped with protection functions against phase failure, voltage deficiency, overvoltage, overcurrent, and short circuit.
◇ When the fire pump starts, the system employs interlock control in the software to ensure that only one pump operates at any given time. In the event of a failure, the system will automatically initiate protection.
LSKSeriesFire inspection cabinetPanel Description
LCD Touch Screen: Displays manual inspection status, automatic inspection status, system failure, equipment operation records, system setting instructions, power supply inspection status
◇ Ammeter: Displays the current value during normal operation
◇ Main Power Indicator Light: Green when AC power is normal
Manual indicator light: shows green during manual inspection
Automatic indicator light: Green during automatic inspection
Controlled indicator light: Red when the pump is running
◇ Start Indicator Light: Red when the pump is in operation
Interlock Signal Indicator Light: Displays red and sounds an alarm when an interlock signal is active
Pump number indicator light: displays red when the corresponding pump is in operation
Emergency Stop Button: A button used to immediately disconnect the control circuit in case of a fault.
Manual/Automatic Button: Manual/Automatic Inspection Switch Button
Bell Release Button: Fault Alarm Mute Button
Fault indicator light: The yellow light is on and an alarm sound is emitted due to the following reasons: A. Overcurrent fault B. Inverter fault C. Power supply fault D. Circuit overvoltage or undervoltage
Product Applications
Product is suitable for daily routine inspections of fire hydrant pumps, sprinkler pumps, and other fire protection facilities in public places or large buildings such as hotels, large shopping malls, supermarkets, high-rise office buildings, cinemas, museums, convention centers, sports venues, airports, train stations, subways, and industrial and mining enterprises. It performs regular, timed, and speed-scheduled inspections on fire pumps, conducts automatic inspections on each unit, ensuring long-term reliable operation of the fire pumps.
Main Technical Parameters of Fire Inspection Cabinet: