For cables jacketed with non-magnetic or tin-plated steel strip (cross-linked polyethylene insulated cables).
Model: YJV62 - Mainly used for fixed installations in distribution networks or industrial plants.
Voltage: 0.6/1 kV
Main Application: The cable can be laid in tunnels or pipelines and can withstand certain pressures.
Cable Structure:
Conductor: Multi-strand copper conductor, CU
Insulation: Cross-linked Polyethylene (XLPE) Inner Lining: Double layer of overlapping PVC wrapping tape.
Sheathed: Double-layer stainless steel steel strip sheathing
Protective Cover: Polyvinyl Chloride (PVC)
Product Features:
The allowable long-term working temperature for the cable conductor is 90°C.
2. During a short circuit (duration not exceeding 5 seconds), the temperature of the cable conductor shall not exceed 250°C.
The environmental temperature during cable laying must not be below 0°C.
4. Cable minimum bend radius: Single-core cable should not be less than 15 times the cable outer diameter.
5. The rated working frequency voltage of the cable is 0.6/1 kV