Applying the rated voltage to the core wire, the current passing through the heating core generates joule heat (Q = 0.24I²RT). A constant power series heating tape utilizes this heat to provide heat preservation for objects requiring companion heating. As the current is consistent at each point, the constant power series heating tape maintains uniform power and temperature. The structure of the constant power series heating tape is simple and easy to maintain, with a length of up to 3KM powered by a single-point power supply. This product must be custom-designed and manufactured based on the pipe length and required power; it cannot be arbitrarily cut on-site.
Constant Power Series Heating Tape Structural Diagram


1. Constant Power Series Resistance Heating Cable Model Description
RDC(Q)-1/2/3-J3/J4-□
□: Heating core single-core cross-section mm
J3/J4: Insulation Code: J3: 205℃; J4: 260℃
1/2/3: Quantity of Heating Cores
Q: Reinforced Outer Sheath
RDC: Constant High Power Series Electric Heating Tape
2. Main Parameters of Constant Power Series Heating Tapes
| Working Voltage | 110~660~1100V |
| Single-core power | ≤18W/m |
| Dielectric strength | 2750V/min |
| Insulation Grade | ≥100MΩ/km |
| Temperature Resistance Grade | F46-205℃;FPA-260℃ |
| Maintain temperature | 0~180℃ |
| Protection Class | IP54 |
| Intrinsically Safe Rating | Exe II C T4 Gb |
| Installation Temperature | ≥-40℃ |
| Bend Radius | ≥5b |
3. Applicable Locations:
Constant power series heating tapes are suitable for anti-freezing and anti-foaming of pipelines and equipment in the following situations:
·Safety Zone
· Hazardous Zones 1 & 2; Zones 21 & 22;
·Humid, salt fog environment; corrosive conditions.