High-temperature Fluoroplastic Copper Tape Shielded KX Compensating Wire ZR-KX-FVP2

Common compensation wires include the following types:

Compensation Conductor

Wire model

Fitted with heat

Thermocouple

Pitch number

Compensation Conductor Alloy Wire

Insulation layer

Coloring

Allowable tolerance at 100℃

℃)

Allowable tolerance at 200℃

℃)





Positive electrode

Negative Pole

Positive Pole

Negative Pole

Standard Grade

Precision grade

Standard Grade

Precision-grade



SC

S

SPC (Copper)

SNC (Copper-Nickel)

Red

Green

±5

±3

±5

-

KC

K

KPC (Lead)

KNC (Copper-Nickel)

Red

Blue

±2.5

±1.5

-

-

KX

K

KPX (Nickel Chrome)

KNX (Nickel Silicon)

Red

Black

±2.5

±1.5

±2.5

±1.5

EX

E

EPX (Nickel Chrome)

ENX (Cupronickel)

Red

Brown

±2.5

±1.5

±2.5

±1.5

JX

J

JPX (Iron)

JNX (Copper-Nickel)

Red

Purple

±2.5

±1.5

±2.5

±1.5

TX

T

TPX (Copper)

TNX (Tungsten-Nickel)

Red

White

±1.0

±0.5

±1.0

±0.5

 

The purpose of using compensation wires:

(1) Move the reference end of the thermocouple from a high-temperature location to a more stable environmental temperature area.

(2) Saves a significant amount of precious and rare metal materials used in the manufacturing of thermocouples.

(3) The use of compensating wires facilitates installation and laying of the lines.

(4) Replacing thermocouple wires with thicker diameters and higher conductivity can reduce the resistance in the thermocouple circuit, benefiting measurement and automatic control.

When using compensating wires, note the following points:

(1) Various compensation wires are only compatible with the corresponding thermocouple models. This means that the thermoelectric properties of each thermocouple and its matching compensation wire must be identical within the specified temperature range (0~100℃).

(2) The temperature at the compensation wire and thermocouple connection point must not exceed the specified operating temperature.

(3) When compensating wires and thermocouples are connected to instruments, the positive and negative poles must not be reversed, and the two pairs of connection points must be at the same temperature.

(4) Select the wire diameter of the compensating wire based on the line resistance requirements of the instruments to be matched.

High-temperature fluoroplastic copper tape shielded KX compensating conductor ZR-KX-FVP2

Disclaimer:Info provided by user, user liable for authenticity, accuracy & legality. Zhongshang114 assumes no liability.

Tip:Confirm supplier qualification & quality before purchase to avoid risks.

Unit Price $4.50 / Rice
Sales None
Delivery AnhuiChuzhou3dayswithin
Stock 10000RiceMOQ1Rice
Brand Wan Trade sincerely
Product Features High-temperature cable
Is Importing No
Origin Tianchang, Anhui
Expiry Long Valid
Update 2023-09-19 13:59
Gallery

Anhui Maocheng Electrical Co., Ltd.Published byHigh-Temperature Fluoroplastic Copper Tape Shielded KX Compensation Wire ZR-KX-FVP2Gallery Lib

Contact Merchant



Join

Successful Enterprise Join, Enjoy Multiple Privileges

Join Hotline:4006299930

Please scan with mobile phone

Customer Service

Service Hotline:4006299930

Official Account

WeChat Official Account, Get Business Opportunities

Scan to follow WeChat

Top