The quality of the cooling water for the electronic radiator must meet the specified requirements. The resistivity of the circulating water should not be less than 2.5 kΩ·cm, and the pH value should be between 6 and 9. The feed temperature should not exceed 35°C, with a water flow rate of 4-8 L/min. When used for high-pressure or high-pressure equipment, it is essential to ensure the above or higher quality of water; when using an electronic radiator, special attention should be paid to prevent leakage, clogging, and condensation upon insertion. When using an electronic radiator, the radiator blades should be installed in the direction of the cooling air flow, with the intake temperature not exceeding 400°C and the intake speed at 4-6 milliseconds.
Raw material quality (purity, thickness, processing accuracy, etc.) is inserted into the radiator. Production process (cracks and shrinkage caused by casting, etc.). Defects such as poor material and roughness will directly affect the heat conduction performance of the radiator; the surface in contact with the platform.