- AllProduct Category
-
Igniter
Flame Monitor
Flame Extinguishing Protection Device
Industrial Boiler Auto Ignition
Torch Ignition Control
Gas Ignition Burner
Torch Tip Series
Oil Gun & Propulsion Series


详情描述

I. Overview:
Xi'an Yanxiang Thermal Energy Technology Co., Ltd. develops and researchesFYXModel series flame detectors are a new generation of intelligent instruments integrated with light, machinery, and electricity. The product introduces cutting-edge foreign optical sensing technology, with stable quality, fast response time, and superior performance; it features small size, light weight, and easy installation. It is a detection instrument for flame detection, gas monitoring, and release system.FYXModel series flame detectors utilize technology, featuring imported sensors and detectors based on microprocessor platforms. They also come standard with flame and fault relays, while offering optional accessories as well.4~20mAAnalog output.FYXModel series flame detectors can exist as standalone devices, directly triggering alarms or driving on-site instruments. Additionally, they can be integrated with various fire control panels,PLCControllerDCSAndEDSAwaiting system interface.FYXFlame detectors, widely used in the power, oil, chemical, and offshore oil platform industries, effectively ensure personal safety and protect national property from damage. Highly praised by a wide range of users.
Section 2: Principle
During the combustion process, combustible materials emit visible light, infrared, and ultraviolet light at different frequencies or wavelengths. In the combustion of gas and heavy oil, the flame emits a major portion of ultraviolet light, followed by visible light and infrared. In the combustion of coal or coal powder, the flame emits a major portion of infrared light. We haveFYXSeries flame detectors: Working principles and application scenarios of different sensors are described as follows:

(1) FYX-1Type UV Flame DetectorUVUtilizing high-sensitivity imported sensors to rapidly detect the majority of flame emissions within this spectral range. The advanced design features anti-light interference capabilities, primarily applied to hydrocarbon flames. Detection distance is:1Square foot gasoline flame500Feet. The company has also developed a fire detection system for heavy residue oil applications.
Applicable scenarios: Furnace, torch, explosives, heavy residual oil, storage areas, dust, etc.
(2)FYX-2Type Infrared Flame DetectorIRThe flame detection is achieved by individually sensing infrared radiation, simultaneously measuring specific infrared frequencies, and then integrating and adjusting them in the circuit to activate alarm outputs and other functions. The infrared flame detector is also immune to sunlight interference, particularly suitable for high-pressure hydrocarbon flames with high concentrations of oil and gas, as well as in environments with floating debris, with a detection distance of1Square Foot Gas Flame150Feet.
Appropriate for environments such as paint spray workshops, offshore oil platforms, and high-pressure gas areas.
(3)FYX-3Type UV/Infrared Composite Flame DetectorUV/IRComprised of a UV and an infrared imported sensor assembly. These two detection units simultaneously monitor different spectral regions, with intelligent recognition and comprehensive judgment. An alarm signal is only output when both probes detect flames. Since these sensors do not have a common alarm source, false alarms from sources such as arc light that could affect either the UV or infrared detector are isolated.XRay and thermal moving objects, etc.FYX-3Type UV/Infrared composite flame detector unaffected. Features a liquid crystal display, menu adjustment, and self-diagnostic function. Suitable for scenarios where single-frequency UV or infrared false alarms may occur. Detection distance is1Square Foot Gasoline Flame300Feet.
Applicable Occasions:成品油储罐区,压缩机泵房,制气厂,石油化工企业,海上石油钻井平台,石油管道等.
Section 3: Technical Specifications
1、 Power Voltage:220VAC/24VDC(Scope18-32VDC)
2、 Operating Current: <100mA(220VAC)
<50 mA (24VDC)
3 、 Spectral Range: UV:160-260nm、250-400nm
Infrared:2.2umLeft and right
4、 Peak Wavelength: UV:210±5nm,360±5nm
Infrared:2.2um
5、 Sensitivity: <10Microlambert
6、 Delay:1~10Instant delay (adjustable on-site)
7、 Applicable Time:80ms
8、 Output Signal: Relay Dry Contact Signal30VDC/1A、220VAC/0.3A(Regularly Open/Normally Closed Field Selectable)
Analog Signal4~20 mA(Option)
9、 Field of View:15℃ (Furnace)45 Torch120 Fire
10、 Associated Equipment: Compatible with safety barriers, valves, and universal joints
11、 Ambient Temperature:-40~+90℃
12、 Relative Temperature: ≤95%No Condensation
13、 Entrance Protection:IP66
14、 Connectivity Cable: Signal Cable
15、 Interface thread:1Pipe Thread (for connection with furnace body)
M20×1.5(Cable Connector)
M12×1.0(Blow-off air connector)
16、 Blow-off Mechanism: Rotating air brush structure to prevent oil and dust from contaminating quartz lens, suitable for harsh working environments.
17、 Outer Dimensions: Φ116×168mm
18、 Net Weight: Aluminum Alloy Shell1.23kg
Stainless Steel Housing1.56kg
Note:1Candlelight flame=Diameter of16mmPlease provide the Chinese content to be translated.1Flame intensity during the combustion of rice.
Four: Installation and Use
(1外形及结构: Appearance and Structure


(2Installation and debugging


Installation diagram torchB

Installation Diagram Tank AreaC
(3Wiring Terminal Diagram:

(4Typical Wiring Example:


(5) Cautionary Notes:
Ensure the hole location when in use.FYXFlame detectors must be aimed at the center of the flame, and positive-pressure furnaces must be equipped with a purification air sweep mechanism. Hainatong Co. Ltd. only provides quick-installation connectors; other fittings are to be supplied by the user. Purification air sweep must be added for the torch flame detector installation. Adjust the sensitivity, delay, zero point, and background on-site. When used as per the manual, the product's lifespan can reach710,000 hours.
Sixth, Principle
Our company is engaged inFYXFlame Detector System Development & Sales of Supporting Equipment, with long-term technical support. We adhere to the principle of "People-Centric," creating ample room for employee development, gathering talents, and collaborating for growth; and with the business philosophy of "ensuring each of our systems is effectively utilized by our customers," we build bridges to success for our clients.
This product comes with a warranty period of12Months, any damage due to equipment quality issues will be repaired and replaced free of charge by our company. Free maintenance outside the warranty period will only incur the cost of the replacement parts.