- AllProduct Category
-
Igniter
Flame Monitor
Flame Extinguishing Protection Device
Industrial Boiler Auto Ignition
Torch Ignition Control
Gas Ignition Burner
Torch Tip Series
Oil Gun & Propulsion Series


详情描述
GYDQ-05High-energy igniters (wired type), designed for automatic ignition of industrial burners. This product is compact, energy-efficient, with a high-temperature-resistant, anti-carbon buildup, and anti-coking firing end, featuring self-cleaning capabilities. It boasts high ignition reliability, outperforming imported ignition transformers. The ignition rod installation is easy, and there's no need to adjust the ignition electrode discharge distance.
I. Technical Specifications:
1.Power Voltage220V±10% 50/60HZ
2.Applicable Fuel: Gas, Light Oil
3.Ignition棒temperature-resistant, long-term1300℃
Section 2: Ignition Device Housing
1.MaterialsABS Impact engineering plastic
2.Volume120×240×70mm
3.Installation Dimensions225×80mmRectangular diagonal installation, mounting holes Φ5mm
Section 3: Illustration of Ignition Device Front Panel

Four, Ignition Lever
1.Ignition Rod Front MaterialkanthalHigh-temperature alloysemicondHigh-Temperature Materials
2.Ignition rod thread installationM18×1.5
3.Ignition rod length is customizable according to customer requirements.
5. Installation and Wiring
The high-energy igniter features a black ignition high-voltage wire and a yellow grounding wire. Simply connect it to the high-voltage cable wire, and the other end to the ignition rod.This ignition rod is a new type structure, requiring no adjustment of the sparking distance, and is long-lasting in temperature resistance.1300℃。
Ignition rod's firing end is mounted in front of the burner nozzle30~50mmFuel burners should be spaced further apart than gas burners.
VI. Usage
1.This ignition device is a high-energy ignition, featuring resistance to carbon buildup. It can still ignite even with carbon accumulation, so users do not need to clean the ignition end during use and can operate it with confidence.
2.Each ignition time must not exceed30sTurn off the ignition power immediately after the flame is lit.
3.The front end of this ignition rod features a special structure; users cannot saw off a section of the rod for use.