- AllProduct Category
-
Igniter
Flame Monitor
Flame Extinguishing Protection Device
Industrial Boiler Auto Ignition
Torch Ignition Control
Gas Ignition Burner
Torch Tip Series
Oil Gun & Propulsion Series


详情描述
FGYD-12Explosion-proof high-energy igniter
FGYQ- High-energy igniter with a 12-volt rating, primarily used for automatic ignition in gas and oil industrial burners. It boasts reliable ignition, long lifespan, and features such as high-temperature resistance at the ignition end, anti-coking properties, and self-cleaning ability.
I. Technical Specifications:
1.Power Voltage: 220V ±10%, 50/60Hz
2.Suitable Fuel: Light Oil, Heavy Oil, Gas
3.Ignition rod temperature resistance: 1300℃
4.Ignition frequency: 6-12 times/s
5.Spark Energy: 12J
6.Exlosion Proof Grade: CT4
II. Ignition Device Outline Dimensions

Section 3: Ignition Rods and Ignition Wires
1.Front end material of the ignition rod: 2520 high temperature alloy; high temperature semiconductor material
2.Ignition rod outer diameter Φ18, installation thread M18×1.0
Ignition cables are specialized high-voltage cables, available in lengths as per customer requirements.
4. Installation and Wiring
1.The ignition rod's firing end is mounted 30 to 50mm in front of the injector (gas) nozzle. This ignition rod is a new structure design, which does not require adjustment of the discharge distance.
2.This series of ignition devices consists of a housing, a specialized high-voltage cable, and an ignition rod. For installation, simply connect the ignition device housing and the ignition rod using the specialized high-voltage cable. Power supply: 220V AC.
3The ignition device must be properly grounded.
Six, Instructions for Use
1Connect power supply, ignition cable, and ignition rod as required.
2Plug in the power, the ignition has started; after ignition is successful, turn off the power.
3.When starting the engine, the ignition device should be turned on first, followed by fuel injection (or air) ignition. Generally, the ignition time should not exceed 30 seconds.
4.When lighting, reduce the auxiliary combustion air and wait until it's lit before gradually increasing the auxiliary combustion air.
5.Fuel should be well atomized; poor atomization quality affects the ignition success rate.
6.Ignition device should rest for 1 minute after operating for 30 seconds to avoid continuous long-term use.
High-energy Igniter Connection Diagram: