SF6The Leak Monitoring and Alarm System is a specialized intelligent online detection system designed in response to the current power system's heightened emphasis on safe production. It is primarily applied to installations with...SF6The electrical distribution room for the equipment is designed to provide personal health and safety protection for staff.
The core function of this system lies in real-time detection of environmental air.SF6Gas content and oxygen content. Once the environmentSF6Excess gas levels or insufficient oxygen triggers an immediate alarm, prompting the system to automatically activate the ventilation fan. Additionally, the system features temperature and humidity detection, voice prompts for operational status, remote alarm, and historical data inquiry among other functionalities.
Utilizing advanced sound velocity principles, the technology enables real-time, quantitative measurement down to50ppm(v/v)The translation of the given content "的" is not possible as it does not contain any Chinese characters that can be translated into English. Please provide the complete Chinese news content for translation.SF6Concentration provides reliable safety assurance for on-site staff. The original imported high-stability ultrasonic sensors and oxygen sensors ensure the accuracy and reliability of measurement results.
The system is widely applicable to various voltage levels.SF6Cabinet rooms, switchgear rooms, and combined electrical roomsGISFacilities such as the transformer room and main transformer room.

Product Features
Advanced Testing Principle: Utilizes the principle of sound velocity for real-time, quantitative measurementSF6Leak gas content, ensure accurate acquisition of gas contentSF6The content surpasses the qualitative judgments of traditional methods.
High Reliability: The dual differential processing method effectively eliminates the impact of temperature and humidity on measurement results, ensuring the stability and accuracy of the measurements, fully complying with the <JJG 914-1996Six Fluoride.SulfurizationIn accordance with the Leak Detector Calibration Procedure requirements.
Safety: Utilized24VDirect Current Power Supply, Avoid Usage220ACPower, ensuring system operation safety.
Multi-Testing Functionality: Not only testingSF6Gas leaks and hypoxia conditions, while also assisting in the detection of environmental data such as temperature and humidity.All.SurfaceMeets the requirements of the "Electric Power Industry Safety Work Regulations."
Early Field Alert Technology: Trace detection technology can trigger early warnings, indicating the location of gas leaks, promptly notifying personnel for evacuation, and protecting operational equipment.
Fieldbus Design: Connects all detection probes and the host via a single cable, enabling highly adaptable discrete or combined configurations.
Single Substation Support for Multi-Point Network Testing54Simultaneous point detection, enhancing efficiency and reliability.
Alarm Record Inquiry Function: The high-capacity data storage allows for the storage of multiple alarm records, facilitating subsequent inquiries and analysis.
Historical Data Recording and Query: The system can store a large volume of measurement data, providing users with historical data query and analysis capabilities.
Infrared Surveillance Feature (optional): Upon staff entering the work area, the system automatically provides voice prompts and displays real-time detection results, enhancing on-site intuitive perception.
Low-Maintenance Design: Optimized electrical design with no need for adjustable components, using high-quality components to ensure long-term stable operation of the system.