60CubicLNGStorage Tank Technical Specifications:
Container Type: IICategory Structure Type: Horizontal Insulation Method: Vacuum Powder Insulation (Pearlescent Sand)
Please provide the Chinese content to be translated into American English. Quality: LNG(Liquefied Natural Gas (LNG) Maximum allowable working pressure:0.86Mpa
Design Temperature: Inner Shell:-196℃ Exterior Shell:-20-50℃
Work Pressure:0.8Mpa Outer Shell:-0.1 MPa Design Pressure:0.84Mpa Outer Shell:-0.1 MPa
Available Accumulated:60m3 Effective Volume:54m3 Material: Inner Liner:S30408 Outer Shell:Q345R
Spec: Inner Shell:?2400×12400×7/8 Outer Shell:?2900×13140×8/10 Total Length:14929mm
Total Weight:21760kg Laminate Spacing:250mm Inner tube material:S30408 Dimensions?2916×14929mm
Insulation Sandwich Material:TCHP-50Matte Pearl Sand Filling Quantity: >30.8m3
Internal Cylinder Pressure Test: Medium: Nitrogen Test Pressure:1.06Mpa
Valves; Low-temperature stainless steel stop valves Sealing vacuum degree: ≤5Pa Static evaporation rate ≤0.316%/d
Vacuum Insulated Sandwich Panel Air Leak Rate ≤2×10-6 Pa.m3/s Vacuum Insulated Jacket Air Leak Rate ≤6×10-5 Pa.m3/s
Manufacturing Acceptance Standards:
GB/T18442.1~18442.6-2011, TSG21~2016"Regulation for Solid Container"NB/T47042-2014
60m3Horizontal Low-Temperature Liquefied Natural Gas Storage Tank Technical Specifications
(2)Tank pipeline valve instrument list (domestic high-quality products)
Serial Number | Name Please provide the Chinese content you would like translated into American English. | Specs | Quantity | Factory Home |
1 | Low-temperature long shaft stop valve | DN40 | 8piece | Zhangjiagang Furui Special Equipment Co., Ltd. |
2 | Low-temperature long shaft stop valve | DN25 | 2Piece | Zhangjiagang Furui Special Equipment Co., Ltd. |
3 | Low-temperature long shaft stop valve | DN10 | 1Piece | Zhangjiagang Furui Special Equipment Co., Ltd. |
4 | Needle valve | DN10 | 2Piece | Zhangjiagang Furui Special Equipment Co., Ltd. |
5 | Pipe safety valve | DN4 | 3Piece | Zhangjiagang Furu Special Equipment Co., Ltd. |
6 | Three-way valve | DN25 | 1Piece | Zhangjiagang Furu Special Equipment Co., Ltd. |
7 | Safety valve | DN25 | 2Piece | Zhangjiagang Furui Special Equipment Co., Ltd. |
8 | Level differential pressure gauge | 15KPa | 1Set | Chengdu Lanshi, Sichuan |
9 | Vacuum Valve Assembly | DN30 | 1Set | Sichuan Chengdu Lanshi |
10 | Oxygen Pressure Gauge | 0-1.6Mpa | 1Piece | Chengdu Tianwei |

Huzhou Boiler Factory Co., Ltd. _ Shandong Hekou Group
Regular inspections
1. The user unit should report for regular inspection to the inspection agency one month before the expiration of the regular inspection validity period. The first regular inspection of storage tanks is generally conducted within three years of their commissioning. Subsequent inspection cycles are determined by the inspection agency based on the safety status level.
2. The user unit and its auxiliary units should carry out technical handling after shutdown and conduct safety inspections prior to testing, ensuring the on-site conditions meet the requirements for the inspection work and prepare accordingly.
During inspections, the unit's safety management personnel, operators, and maintenance staff should be present to assist with the inspection, promptly provide relevant documents, oversee safety, and establish reliable communication methods.
Safety Protection
The potential hazards in the operation of liquefied natural gas primarily stem from its physical properties:
Liquefied natural gas has an extremely low temperature at atmospheric pressure: -162°C.
High gas-liquid volume ratio; improper pressure relief measures can lead to rapid pressure increase. The gas-liquid volume ratio of liquefied natural gas is approximately 620:1.
Natural gas is an asphyxiating gas.
Natural gas is a flammable gas (ignition point 538°C).
Explosions may occur in confined spaces (explosive limits in air: 5.3% to 15%)
2. When working at a site with natural gas or liquefied natural gas, the following safety knowledge is required:
Keep liquefied natural gas equipment away from flames or electric sparks.
No smoking or open flames are permitted in areas involved in Liquefied Natural Gas equipment maintenance, refueling, and storage.
When working in areas with liquefied natural gas, protective goggles, face shields, and insulated gloves must be worn. Pants should not be tucked into boots, sleeves should not be worn inside insulated gloves, and boots should not have nails.
During dismantling and component maintenance, the liquefied natural gas tank must be emptied and depressurized.
Tools used for maintenance should not produce sparks.
3. Warning
Protect eyes and exposed skin.
Maintain good ventilation in the area where the equipment is located.
Ensure the system is depressurized when repairing or maintaining equipment.
Keep away from flammables or electric sparks.
The root valve must be kept constantly open.



Special Price LNG Storage Tanks Custom-Made - Supply LNG Storage Tank Prices - Professional LNG Storage Tank Production Prices - Ready-Made LNG Storage Tank Processing Factory