Shenzhen ZhongNuo Testing Technology Co., Ltd. specializes in the calibration, verification, and measurement services for gas alarms, flammable gas detectors, toxic and harmful gas detectors, and other equipment in various locations. We hold qualifications to serve nationwide, addressing clients' electrical safety and explosion-proof fire prevention issues, and contributing to safe production.
How often should various gas detectors be calibrated and tested?
Instrument recalibration is typically every 1 year, determined by the submitting unit based on actual usage. During the secondary calibration process, if there are doubts about the instrument's test data, or if the main components of the instrument are replaced, or if recalibration is needed after repairs.
Gas Detector Alarm Calibration Specification Requirements
Regulation 5.5 of the "Regulation for Calibration of Combustible Gas Detectors" (JJG693-2011) states: The calibration cycle for combustible gas detection and alarm instruments: Generally, the calibration cycle of the instrument should not exceed one year. Instruments with suspected measurement data, instruments that have replaced major components, or instruments that have been repaired should be submitted for calibration promptly.
Section 3.5 of "Code for the Use of Combustible Gas Detection and Alarm Systems" (SY6503-2000) stipulates: The combustible gas detection and alarm systems in use shall be calibrated periodically as per regulations.
Occupational Health and Safety Code for Toxic Gas Equipment Installation (GBZ/T223-2009) Article 7.2.1 stipulates: Calibration of detection and alarm devices shall be conducted regularly according to the manufacturer's specified time and procedures.
Regulation 3.4 of the "Code for the Use of Combustible Gas Detectors and Alarms" (SY6503-2000) stipulates: Combustible gas detectors and alarms for installation and use should have measurement instruments manufactured by an institution recognized for their**explosion-proof performance**.
Standard for Verification and Calibration of Flammable and Toxic Gases Detectors:
GB/T50493-2019 "Design Standard for Detection and Alarm Systems of Combustible Gases and Toxic Gases in Petroleum and Chemical Industries"
GB12358-2006 General Technical Requirements for Environmental Gas Detection and Alarm Instruments in Workplace
JJG693-2011 "Regulation for Calibration of Combustible Gas Detectors"
What does a calibration report for a flammable gas detector typically include?
The results of the inspection should be reflected in the inspection certificate or report, and the inspection proof or report must include the following information.
① Calibration Certificate or Calibration Report
② Laboratory Name and Address
③ Calibration Location (if not calibrated in the laboratory)
④ Certificate or report (e.g., numbered), indicating each page and the total number of pages;
5. Send the company name and address.
⑥ Describe and clearly define the target school.
Calibration Date and Receipt Date
⑧ Technical specifications for calibration foundation, including names and codes;
Description of traceability and effectiveness of the measurement standards used for calibration.
⑩ Description of Calibration Environment
11. Calibration Results and Measurement Uncertainty Statements
12. Signature, title, or equivalent symbol of the issuer of the calibration certificate or report, and the issuance date;
13. Calibration results are only applicable to the calibration object.
14. No part of the certificate or report may be copied without written consent from the laboratory.
Re-review time interval
Instrument recalibration is typically every 1 year, determined by the submitting unit based on actual usage. During the secondary calibration process, if there are doubts about the instrument's test data, or if the main components of the instrument are replaced, or if recalibration is needed after repairs.
Shenzhen ZhongNuo Testing Technology Co., Ltd. is a third-party institution specializing in electrical safety, electrical explosion-proofing, gas alarms, and toxic and harmful gas detection instruments, offering regular inspections, metrological services, and calibration. We are qualified to help clients address fire and explosion prevention issues.