Shenzhen ZhongNuo Testing Technology Co., Ltd. specializes in the certification, calibration, and metrological services for equipment such as gas detectors, combustible gas sensors, and toxic gas detection instruments for various locations. We offer qualifications and services nationwide, addressing electrical safety and explosion-proof fire prevention issues for clients, and supporting safe production.
Gas Detector Alarm Calibration Specification Requirements
Regulation 5.5 of the "Regulation for Inspection and Verification of Combustible Gas Detectors" (JJG693-2011) states: The inspection cycle for combustible gas detection and alarm instruments: The general inspection cycle for the instrument should not exceed one year. If there is any doubt about the instrument's measurement data, or if the instrument has been replaced with major components or repaired, it should be submitted for inspection promptly.
Section 3.5 of the "Regulations for the Use of Combustible Gas Detection and Alarm Systems" (SY6503-2000) stipulates: The combustible gas detection and alarm systems in use shall be calibrated regularly as required.
Occupational Health Service Station Standard for Toxic Gas Devices (GBZ/T223-2009) Article 7.2.1 stipulates: Calibration of detection and alarm devices shall be carried out regularly according to the manufacturer's specified time and procedures.
Regulation 3.4 of the "Code for the Use of Combustible Gas Detectors and Alarms" (SY6503-2000) stipulates: Combustible gas detectors and alarms for installation and use should have measurement instruments manufactured by an authorized body and **explosion-proof performance**.
Gas alarm regular inspection contents
Installation spacing of inspection (testing) points
2. Installation Height of the Detector
3. Indicated Error (Concentration)
4. Repeatability (Concentration)
5. Alarm Error (Concentration)
6. Response Time (Seconds)
Key Technical Requirements for Regular Calibration of Combustible Gas Detectors (Shenzhen ZhongNuo Testing Technology Co., Ltd.)
1. Power-On Self-Check Function: The instrument should have an automatic self-check function upon startup, with a manual self-check function for alarm components as well.
2. Specify the effective detection distance: The effective detection distance of the non-contact gas alarm instrument shall not be less than 20 m.
3. Alarm Value Setting: Specific alarm value settings are standardized for different gases.
For example, the hypoxia alarm setting is 19.5% VOL, and the hyperoxia alarm setting is 23.5% VOL (refer to GB 8958-2006 "Operation Code for Hypoxia Hazardous Work" and GB 30871-2022 "Special Operation Regulations for Hazardous Chemical Enterprises").
The first-level flammable gas alarm setpoint is not greater than 25% LEL, and the second-level alarm setpoint is not greater than 50% LEL.
The first and second-level alarm settings for toxic and harmful gases are determined based on OEL (Occupational Exposure Limit) or IDLH (Immediately Dangerous to Life and Health).
4. Error and Repeatability: The standard specifies clear requirements for the instrument's indication error, drift, and repeatability. For instance, the indication error for flammable gases, toxic and harmful gases, and oxygen should not exceed 5% FS, 5% FS, and 2% FS respectively within the normal test range of the instrument's full scale.
5. Calibration and Interface: The instrument should be easy to calibrate, with a set calibration program and corresponding interface to ensure the accuracy of its measurement results.
6. Explosion-proof Performance: Equipment used in explosive environments must have explosion-proof performance in accordance with relevant regulations and obtain an explosion-proof certificate.
7. Audio-Visual Alarm Device: The alarm's audio-visual alarm device must meet visibility and sound pressure level requirements under specific conditions to ensure effective alerting of staff during emergencies.
8. Output Control Function: Instruments with output control capabilities should activate the output control function upon emitting an alarm signal, such as cutting off power or initiating an exhaust system, etc.
9. Power Requirements: Specific requirements are outlined for the power supply voltage, continuous operating time, etc., of battery-powered and non-battery-powered instruments.
10. Other Performance Requirements: Includes requirements for azimuth, response time, full-scale indication error, high-speed airflow, long-term stability, insulation withstand voltage, temperature, constant humidity and heat, electromagnetic interference resistance, steam interference resistance, vibration and drop resistance, and functionality.
Routine Inspection Items for Workplace Environmental Gas Detection and Alarm Equipment
Alarm sound and light (if applicable)
2. Low response value
3. Indicating Error (for Gas Detectors/Gas Detector Alarms)
4. Instrument Drift (in Portable Instruments)
5. Alarm Error (for Gas Detector/ Gas Alarm)
6. Pump-Actuated Instrument Gas Sampling Distance and Flow Rate (for Pump-Actuated Instruments)
7. Power Supply (for battery-powered instruments)
8. Response Time
9. Status Indicator (with Wireless Communication Function)
Shenzhen Zhongnuo Testing Technology Co., Ltd. is a third-party institution that specializes in electrical safety, electrical explosion-proofing, gas alarms, and toxic and harmful gas alarm instruments, providing regular verification, measurement, and calibration services. We hold the necessary qualifications to address fire and explosion prevention issues for our clients.