OBO Surge Protection Device, FLD24 Signal Surge Arrester, 24V Industrial PLC Surge Module


Performance
| Usage Advantages
|
Mounted on 35mm track
| Directly install inside the distribution box or switch box
|
Available for remote alarm (VF 230/-FS)
| Surge protector with sustainable monitoring of operational status
|
Screwless terminal block
| Easy to install
|
Y-type circuit
| For safer surge protection on the phase line, neutral line, and ground line.
|
Features and Application Fields OBO FLD surge protectors are overvoltage protection components for engineering control systems, signal flow loops, transmission line systems, and computer systems. The surge protectors in the VF series feature a voltage-sensitive resistor in the protected circuit, which ensures a very low protection level under the limited discharge current of the FKA. The circuit includes a gas discharge tube and a zinc oxide varistor, monitored by a thermal fuse. In case of aging or overload of the surge protector's internal components, the built-in circuit breaker will immediately disconnect the circuit, and the green status indicator will turn off. If the protection device is equipped with a remote signal alarm unit (FS), it will activate a floating changeover contact.
|
Installation The OBO FLD series surge protectors can be directly mounted on a 35mm standard rail using a mounting clip. They can be connected to remote signal indicators via the provided plug-in connectors.
|
Operating Voltage: UN
| 24V(50-60HZ)
|
Sustainable Working Voltage UC
| 255VN
|
LPZ Zone
| 2→3
|
Meets DIN VDE 0675/6 (11.89) A1, A2/IEC 61643-1
| D Grade/Class III
|
Rated Load Current IL
| 20A
|
Rated Discharge Current In
| 2.5KA
|
Discharge Current Imax
| 7KA
|
Voltage Protection Level UP L-N UP L/N-PE
| ≤1.0KV ≤1.5KV
|
Cross-sectional connection line
| 0.14-2.5mm2
|
Strip Length of Wires
| 6-7mm
|
Response Time: TA
| <25 ns
|
Color Materials Installation
| Grey, RAL 7035 Imide 6 | Duroplast 可直接安装在35mm导轨上,符合DIN EN 50 022标准。
|
| Prices listed on this link are for reference only. Due to various styles and requirements, actual prices should be confirmed via online inquiry, phone quote, or written quote. For more detailed information, please contact the relevant business personnel. Thank you! |