Technical Specifications
Model and Specifications: ZYAFD
Input Power: AC 220V ±15%, 50Hz
■ Input Power: 45W
Communication Method: RS485 Bus
■ Power Cable: NH-RVS-2x2.5mm2
Communication Bus: RWP2x1.0mm2
Communication Distance: Reliable communication up to 1200m; beyond 1200m, extension via local PBX and expansion of sensor capacity is available.
■ Power Supply Distance: <500m; over 500m can be extended through local branch exchanges
Output Interface: 1 RS485 port, connection cable <1000m (extendable)
1 Single-line control output, output is a connected normally open contact
Alarm Function: Audio and visual alarms, displaying alarm address and fault type
Password Function: Operates with different levels of access, suitable for分级 operation by personnel of varying levels
Display Function: Full Chinese LCD Graphical Display & LED Indicator
Printing Function: Mini thermal printer, Chinese character printing (optional)
Storage alarm records: >5,000 entries
■ Dimensions: 400*500*140mm
Key Features
■ Complies with the national standard GB14287.4-2011 "Part 4: Faulty Arc Detectors of Electrical Fire Monitoring Systems" requirements
Connects with master stations, local branch exchanges, sensors, etc., for flexible construction of a high-capacity arc fault monitoring system
The system operates in an open mode, self-managed within, and transmits information unidirectionally externally.
■ Utilizes distributed power supply, with the detector powered independently, ensuring the system's stability and safety effectively.
The output loop can be flexibly expanded through local branch exchanges, adapting to the complex and variable requirements of modern buildings.
Real-time monitoring of all tested circuit currents, voltages, arc states, and fault information, and transmitting working status and alarm messages to the display device.
Dimensions Diagram