Technical Specifications
Model and Specification: ZYYK-Y300B
■ Working Voltage: AC 220V ±15%, 50Hz
■ Power Consumption: ≤25W (excluding control unit)
Backup Power: 12V/4.5Ah (1 pc)
Communication Method: CAN Communication
Transmission Distance: ≤1000m (2X1.5mm²)
■ Display Mode: 7-inch Color Screen Display
Alarm Method: Audio-Visual Alarm
Output Interface: Two sets of switch quantity output
Dimensions: 400 x 500 x 140mm
■ Weight: 9kg (including battery)
■ Installation Method: Wall-mounted
Feature highlights
Monitor remaining pressure controller, air valve actuator, and remaining pressure detector status.
Alarming function, security protection feature, historical operation records of monitors, system self-check, reset and restart function
Standard of Execution
China National Standard GB50016-2014 "Code for Fire Protection of Building Design"
China National Standard GB51251-2017 "Technical Standard for Smoke and Smoke Exhaust System in Buildings" Article 3.4.4: The mechanical pressure supply air volume should meet the increasing pressure distribution from the corridor to the ante-room to the stairwell, and the excess pressure value should comply with the following regulations:
(1) The pressure difference between the antechamber, enclosed refuge (room), and corridors is 25Pa to 30Pa.
(2) The pressure difference between the stairwell and corridor is 40Pa to 50Pa.
(3) When the system's remaining pressure exceeds the permissible pressure difference, depressurization measures should be taken.
(4) Mechanical pressure-air supply systems should be equipped with pressure measurement devices and air pressure regulation measures.