Electro-hydraulic Valve Actuators SKD32...SKD82...SKD62...SKD60
20mm行程
• SKD32...: Operating voltage is AC 230V, three-position control signal
• SKD82...: Operating Voltage AC 24 V, Three-Way Control Signal
• SKD6…: Operating voltage is AC 24V, DC 0-10V, 4-20mA, or 0-1000Ω valve signal
• SKD6...: Selectable flow characteristics, valve position feedback, stroke adjustment, LED status indication, priority control
• SKD62UA: Featuring sequential control with selectable action direction, stroke limit control, adjustable starting points and stroke range, as well as additional freeze protection monitoring signals QAF21... and QAF61... etc.
• Drive force reaches 1000 N
• With or without spring return feature
• Directly mounted on the valve, no adjustment required
• Manual adjustment and position indication features available
• Functionality can be enhanced with additional auxiliary switches, potentiometers, valve stem heaters, and stroke inverters.
• SKD...U with UL Certification
Usage
For Siemens two-way and three-way valves in the VVF...、VVG…、VXF… and VXG... series, featuring a 20 mm stroke, these are used in HVAC systems as control valves or safety shut-off valves.
Engineering Precautions
The electrical connection of the actuator must comply with local electrical installation regulations and internal wiring diagrams. To ensure personal and property safety, it is mandatory to adhere to the corresponding safety regulations and limitations! An ASZ6.5 stem heater must be used when the medium temperature is below 0°C to prevent valve freezing. For safety reasons, the stem heater is designed for AC 24V / 30W.
The actuator bracket and valve rod cannot be isolated to ensure air circulation. Do not touch hot components without protective measures to avoid burns.
Failure to follow the above suggestions may cause accidents or fires.
Recommendation: Strongly recommend isolating the valve when the temperature exceeds 140 °C.