LRD-1151GP Capacitive Pressure Transmitter
Technical Specifications:
Transfer Amount: Maximum positive transfer is 500% of the minimum adjustment range; maximum negative transfer is 600% of the minimum adjustment range.
Overpressure Limit: Applied pressure ranges from 0 (absolute pressure) to 3.8 MPa for the range up to 200 kPa; from 0 (absolute pressure) to 13.8 MPa for the range below 6.89 MPa; from 0 (absolute pressure) to 31.4 MPa for the range of 20.7 MPa; and from 0 (absolute pressure) to 51.4 MPa for the range of 41.3 MPa. The transmitter is undamaged and operates normally at pressures above 3.4 kPa (absolute pressure), and the flange can withstand a pressure of 68.9 MPa.
Temperature Influence: Maximum Range Zero Error: 0.5% of range at 55℃; Minimum Range Zero Error: 3.0% of range at 55℃
Installation Position Impact: Can cause ±0.25 kPa zero-point error, but it is correctable and does not affect the range.
Weight: 5.4 kg (excluding options)

Structural Dimensions:
Installation Type:

Wiring Method: