Virtus UPS GXE Features:
Breakthrough ultra-compact design: 30%-70% smaller than similar products; Large LCD display for direct and convenient settings; Output does not drop within the input voltage range of 120-288V, significantly reducing the likelihood of battery conversion and extending battery life; Overload capacity: At rated line power, 130% for 10 minutes, 150% for 1 minute, meeting customers' sudden load requirements; 8A long machine charging capability, with adjustable charging power to quickly recharge long-duration batteries, enhancing battery life; Outstanding environmental and energy-saving features, efficiency up to 3-4 percentage points higher than similar products, and can save nearly 1 kWh per day under full load.
Parameters | Product Model | |||
| GXE01k00TS1101C00 GXE01k00TL1101C00 | GXE02k00TS1101C00 GXE02k00TL1101C00 | GXE03k00TS1101C00 /GXE03k00TL1101C00 | ||
| Model Grade | 1000VA/800W | 2000VA/1600W | 3000VA/2400W | |
Input | Voltage Range (Rated) | 120Vac ~ 288Vac, rated at 220Vac, can operate at full load across the entire input voltage range | ||
| Power Factor | 0.99 | |||
| Frequency | 45Hz to 65Hz; Adaptive | |||
Output | Voltage | 220Vac±1%,230/240Vac±3% | ||
| Power Factor | 0.8 | |||
| Frequency | 45Hz to 55Hz (50Hz system); 55Hz to 65Hz (60Hz system) | |||
| Waveform | Sine Wave | |||
| Current Peak Factor | 3:1 | |||
| Voltage Distortion | ≤3% rated linear load, ≤5% rated non-linear load | |||
| Overload Capacity | Rated Input: 105% to 130%, 10 minutes; 130% to 150%, 1 minute; >150%, 500ms | |||
Battery | Type | Valve-regulated Lead-Acid Battery | ||
| Quantity * Voltage * Capacity | 3x12Vx7Ah (Standard Machine) | 6x12Vx7Ah (standard machine) | 6x12Vx9Ah (Standard Machine) | |
| Backup time for standard battery | >4 min | |||
| Charging Current | Long Machine 8A Max (automatically matches charging current based on user-set battery capacity) | |||
| Recharge time | Discharge to shutdown with UPS, charge to 90% of battery capacity in 6 hours (standard model) | |||
Environment | Operating Temperature | 0℃~+40℃ | ||
| Storage Temperature | -40℃~+70℃ | |||
| Relative Humidity | 0% RH to 95% RH, No Condensation | |||
| Working Altitude | At 40°C, up to 6,600 feet (2,000m) without derating | |||
| Noise | <45dB | |||
Communication and Management | Communication Interface | DB-9, 232, Type B USB | ||
| SNMP Remote Management | Optional External SNMP | |||
| Installation Method | Tower | |||
| Switch Time | 0ms | |||
| Overall Efficiency (City Power Mode) | ≥91% | ≥93% | ||
| Safety Regulations | EN62040-1:2008 | |||
Electromagnetic Compatibility | CE/RE | IEC/EN/AS 62040-2 2nd Ed =CISPR Class A | ||
| surge | IEC/EN 61000-4-5, Level 3 (2kV) (L, N to ground), Level 2 (1kV) (L, N between) | |||
Dimensions (Width x Height x Depth, mm) | bare unit | 156×255×295 (standard machine) | 156×255×466 (Standard Model) | 156×255×466 (Standard Model) |
| 156×150×295 (Length Machine) | 156×150×466 (Length Machine) | 156×150×466 (Length Machine) | ||
Weight (kg) | Naked Machine | 12 (Standard Machine) / 4 (Long Machine) | 22 (standard machine) / 7 (long machine) | 25 (standard machine) / 7 (long machine) |
| Packaging | 13 (Standard Machine) / 5 (Long Machine) | 24 (Standard Machine) / 8 (Long Machine) | 27 (Standard Machine) / 8 (Long Machine) | |
| Color | Black RAL 7021 | |||
Virtus UPS GXE03k00TL1101C00 Load and Delay Time
| 1KVA (0.8KW) | 2KVA (1.6KW) | 3KVA (2.4KW) | |
| Standard Model | 12m (half load) / 4.8m (full load) | 12m (half load) / 5.2m (full load) | 11.5m (half-load) / 4.5m (full-load) |
| 12V/24Ah×1 | 32m | 32m | 18m |
| 12V/38Ah×1 | 50m | 50m | 33m |
| 12V/65Ah×1 | 1h30m | 1h30m | 1h10m |
| 12V/75Ah×1 | 2h4m | 2h4m | 1h25m |
| 12V/100Ah×1 | 2h45m | 2h45m | 1h32m |