Overview and Principle
This product is suitable for indoor use in buildings and similar facilities with a 50Hz AC, rated voltage of 380V, and rated current not exceeding 80A, providing isolation protection for low-voltage terminal power distribution in industrial, commercial, residential, and infrastructure applications, and is also suitable for infrequent switching operations.
Applicable working environment and installation conditions
Ambient Temperature: -15℃
∼40℃
Relative Air Humidity: ≤95% (No Dew Condensation)
Altitude ≤ 2000m
Pollution Level: 2
Areas with no significant vibration or shock
Product Features
Short Circuit Protection: The circuit breaker trips and shuts off power in 0.04 seconds upon a short circuit.
Type C instantaneous trip current:

D-Type Instantaneous Trip Current:

Interrupting Current: lcs = lcn ≥ 6000A
Overcurrent (Overload) Protection:

Key Performance Indicators
Rated Voltage: AC 380V
Rated Line Current: 80A, 63A, 32A
Detent Characteristics:
C-type instantaneous trip current, 5-10In
D-type instantaneous trip current, 10-14In
Wiring Capacity
Wires with a cross-sectional area of 25mm² or less
Meets standards
GB/T10963.1
Product Selection Sheet

Dimensions