Overview and Principle
This product is suitable for indoor applications, providing isolation protection for low-voltage distribution in industrial, commercial, residential buildings, and infrastructure in buildings and similar locations with an alternating current frequency of 50Hz, rated voltage of 220V, and rated current not exceeding 80A. It is also suitable for infrequent switching operations.
Applicable Working Environment and Installation Conditions
Ambient Temperature: -15°C to 40°C
Relative Air Humidity: ≤95% (non-condensating)
Altitude ≤ 2,000m
Pollution Level: Level 2
Areas with no significant vibration or shock
Product Features
Short-circuit Protection: The circuit breaker disconnects and protects within 0.04 seconds upon a line short-circuit; Type C instantaneous trip current

Interrupting Current: lcs = lc ≥ 6000A
Overcurrent (Overload) Protection:

Key Performance Indicators (KPIs)
Rated Voltage: AC 220V
Rated Current: 80A, 63A, 32A, 16A
Detent Characteristics: Type C instantaneous detent current, 5-10In
Wiring capability
25mm² and below wire
Meets Standards
GB/T 10963.1
Product Selection Chart