BHG-YSP Transformer Oil Chromatography Online Monitoring System Brief Introduction
BHG-YSP Transformer Oil Chromatography Online Monitoring System features automatic quantitative recycling cleaning, oil intake, oil-gas separation, and sample
Product analysis, data processing, real-time alerts; rapid online monitoring of transformer and other oil-immersed high-voltage electrical equipment for dissolved gases.
The content of the obstacle gas and its growth rate, and by using a fault diagnosis expert system to early predict potential equipment fault隐患 information, to avoid equipment
Accidents, minimize significant losses, and enhance the reliability of equipment operation. This system serves as the new generation product in the field of oil chromatography online monitoring.
Products, offering a stable and reliable solution for online remote DGA analysis of power transformers, ensuring the condition of the power system
Robust guarantee for the implementation of the maintenance system.
The BHG-YSP system integrates years of successful experience from our company's operation of the electric chromatography automatic full degassing device.
Summarizing the advantages and disadvantages of on-line oil chromatography monitoring at home and abroad, meticulously crafted. This system maintains the characteristics of our company's products that have always been present.
Advantages in stability, reliability, and accuracy:
♦ Online detection of concentrations and growth rates for H2, CO, CO2, CH4, C2H4, C2H2, C2H6, and H2O (optional).
♦ Quantitative cleaning cycle sampling method, truly reflecting the dissolved gas status in transformer oil.
♦ Oil and gas separation is safe and reliable, non-polluting; users can choose to discharge or not discharge transformer oil.
♦ Utilizes composite chromatographic column to enhance separation of gas components;
♦ Utilizing imported, specially designed detectors to enhance the sensitivity of hydrocarbon gas detection.
♦ High stability and precision gas detection technology with an error range of ±10%;
♦ Mature and reliable communication methods, utilizing standard network protocols, supporting remote data transmission.
♦ High reliability data collection, utilizing delta-sigma ADC with over-sampling technique, 24-bit resolution, auto-calibration.
♦ Varied data display and query options, including reports and trend charts, with a 10-year lifespan for historical data storage.
♦ Highly adaptable to various environments, successfully applied in cold, hot, humid, and high-altitude regions.
High anti-interference performance, electromagnetic compatibility meets GB/T17626 and IEC61000 standards.
♦ Offers two-level alarm function with remote transmission capability.
♦ Open database, capable of connecting to the local area network of the power system.
Additionally, the BHG-YSP system features a modular design, with the application of high-performance embedded processors enabling on-line chromatographic monitoring.
Measurement System
The system is more stable and reliable, featuring the following characteristics:
♦ Faster analysis cycle, with a small monitoring period of 40-60 minutes, customizable by the user, recommended monitoring cycle
Check every 24 hours.
♦ Fast oil and gas separation, taking about 10 minutes or so, with special environmental adaptation technology, eliminating temperature and humidity
The effect of temperature variation on the gas distribution coefficient.
♦ Analyzed oil samples are treated with degassing and buffering techniques to eliminate air bubbles mixed in the oil samples of the transformer's main body.
Multi-layer insulated return oil (return oil) technology ensures that the carrier gas will not enter the transformer body.
♦ C2H2 detection limit as low as 0.1-0.5 μL/L
♦ Equipped with dual-circuit multi-mode temperature control, achieving ±0.1℃ temperature accuracy, and featuring an automatic temperature control industrial air conditioner.
♦ Embedded processor control system for oil-gas separation, data collection, chromatographic analysis, concentration calculation, and data
All-in-one alarm and equipment status monitoring, ensuring no data loss occurs, significantly enhancing the system's reliability.
Sexuality and stability;
♦ The functional interface circuit employs optocoupler isolation design to further enhance the system's anti-interference performance.
♦ Utilizes Ethernet for full digital, remote data transmission, control, and parameter settings.
Enhanced system fault diagnosis function, offering improved three-ratio method, David Triangle method, and cube diagram approach, providing diagnostic
Inconsistent results;
♦ Enhance system self-inspection, add remote maintenance capabilities, and provide alarm for equipment abnormal events.
♦ Supports IEC 61850 communication protocol, offering networking functions for similar monitoring equipment, enabling centralized remote diagnosis in a specific area.
Broken
♦ The system structure features a 19" standard cabinet and a highly integrated modular design, offering a compact structure, easy installation and maintenance, and user-friendly operation.
Humanized
Highly scalable, easily integrated with other monitoring devices.
♦ Bottleless design; no need to replace the carrier gas annually, significantly reducing after-sales maintenance volume, and no high-pressure containers involved.
Adjacent to the transformer, equipment safety is fully ensured with no potential safety hazards.
BHG-YSP Transformer Oil Chromatography Online Monitoring System Composition
BHG-YSP Transformer Oil Chromatography On-line Monitoring System can be independently completed by the field monitoring host, which includes
Chromatography Data Acquisition and Processing Module, Oil and Gas Separation Module, Gas Detection Module, Gas Source Module, and four high-integration auxiliary modules
Assist unit composition. The Chromatography Data Acquisition and Processing Module includes data acquisition unit, on-site control and processing unit, and communication control
Unit and 61850 protocol communication; oil and gas separation module includes oil sample circulation collection unit, oil sample quantitative unit, and oil sample processing
Return units, degassing collection units, etc.; the gas detection module includes gas separation units, constant temperature and constant current control units, and gas detection components.
Test units; the gas source module includes gas production units, gas storage units, purification units, pressure control and alarm units, etc.; auxiliary units
The price includes the placement of transformers at the interfaces, oil pipes, communication, and power cables.
If not directly uploading data and alarms via the IEC 61850 communication protocol, computers and monitoring software can still be installed in the main control room.
Monitor the equipment's operational status directly within the main control room. Principle of operation for the BHG-YSP Transformer Oil Chromatography Online Monitoring System.
The BHG-YSP Transformer Oil Chromatography Online Monitoring System, during operation, initially uses the oil sample collection unit to circulate the oil path.
Treat the dead oil in the pipeline connections, then perform quantitative oil sampling; the oil-gas separator rapidly separates dissolved gases in the oil and transports them to the six-way valve.
The sample is automatically introduced into the quantitative tube; under the propulsion of the carrier gas produced in-house, the sample gas passes through the chromatographic column for separation and sequentially enters the gas detector.
Data collection unit completes the conversion and collection of AD data, while the embedded processing unit stores and calculates the collected data.
Calculate and analyze, and upload the data to the data processing server via a 100M Ethernet interface or directly through communication protocols.
Data transmission to the provincial company's backend can also be handled and fault analysis performed by the BHG-YSP-03 Monitoring and Early Warning software.