Technical Specifications
■ Model and Specifications: ZYDF-Y/F
Rated working voltage AC 220V 50Hz;
The residual current alarm value is adjustable from 50mA to 999mA with a continuous step of 1mA. Holding it for 2 seconds allows for a quick increase.
■ Protection action time: ≤0.5s
Alarms activated: ≥70db
Alarm and release output: switch type, contact capacity AC250V/5A
■ Operating Environment Conditions ①Ambient Temperature: -10°C to +40°C ②Relative Humidity: 10% to 90% Control
System Functions
Real-time monitoring
Leakage current-based electrical fire detection sensors enable real-time monitoring and display of the residual current in controlled circuits.
Alarm Protection Feature
Residual Current Electric Fire Monitoring Detectors can detect the residual current of electrical circuits. If the limit is exceeded, they emit audio-visual alarms. They can also cut off the power supply circuit within the specified time (can be set not to cut off) to ensure safe electricity use.
Communication Features
The residual current electrical fire detection sensors are equipped with RS485 communication bus and Modbus-RTU protocol, enabling network communication with our company's monitoring equipment host for remote management and maintenance.
Product dimensions and wiring connection diagram