- AllProduct Category
-
Explosion-proof Electric/Steam/Hot Water Heater Blowers
Humidifier and Dehumidifier in One
Rotary Dehumidification Unit - Customized
Mobile Air Conditioner/Portable Air Cooler
Fan Coil Unit/Air Handling Unit
Smart Dehumidifier Unit
Explosion-proof Modular Air Handling Unit / Swimming Pool Dehumidifying Air Handling Unit
Explosion-Proof Rooftop AC Series
Explosion-Proof Cold Water (Hot Water) Unit Series
Explosion-Proof Oven
Explosion-proof Air curtain Machine
Explosion-proof Temperature and Humidity Control Unit/Non-standard Temperature and Humidity Control System
Industrial Air Conditioning / Explosion-proof Industrial Air Conditioning
Cabinet Air Conditioners / Explosion-Proof Cabinet Air Conditioners
Explosion-proof Fan Coil Unit
Explosion-Proof Refrigerator
Explosion-proof Air Conditioner
Explosion-Proof Dehumidifier
Humidifier/Blast-Proof Humidifier
Dehumidifier


详情描述
The Yingteng FP series fan coil units incorporate advanced technologies from similar products domestically and internationally. Compliant with national standards and after numerous trials and tests, they have efficiently completed a series of technical design improvements. As a result, they offer superior performance, wide applications, a complete range of types, high efficiency, and low noise. The series includes horizontal concealed, horizontal exposed, vertical concealed, vertical exposed, and cassette units. When paired with fresh air handling units, they are extensively used in low-noise environments such as hotels, hospitals, office spaces, high-end conference halls, and exhibition halls, making them an ideal terminal device for centralized air conditioning systems.
Product Specifications
Model: FP68 (WM)
Brand: YingTeng
Airflow (m³): 680
Cooling Capacity (W): 3600
Heat (W): 5400
Noise db(A): ≤41
Cold Water Supply Temperature: 7℃-12℃
Hot Water Supply Temperature: 40℃-60℃
Working Pressure (KPa): 1.6
Static Pressure: 30Pa/50Pa
Power Supply: 220V/50Hz
Inlet and outlet pipes: ZG 3/4
Condensate Drain Pipe: ZG3/4
Dimensions (Length x Width x Height mm): 980 x 500 x 250
Note: The data in the table are measured values under the test conditions specified in the national standard for "Fan Coil Unit" (GB/T19232-2003).
1. Cooling supply conditions parameters: Inlet dry bulb temperature DB = 27°C, wet bulb temperature WB = 19.5°C.
Cold water intake temperature: 7℃, outlet water temperature: 12℃。
Heating工况parameters: Imported air dry bulb temperature DB=21℃, incoming water temperature 60℃.
2. Noise Measurement: Values measured at 1 meter forward and 1 meter up/down from the front of the unit within the anechoic chamber.
3. Standard configuration of the vertical concealed unit features an outdoor static pressure of 12 Pa.
4. Water resistance refers to the resistance at the rated flow rate; input power refers to the power input at high airflow.
5. When selecting a combination cold and hot twin tube unit, refer to the main technical parameters in the table above. One row of heat is approximately 40% of three rows of heat, low static...
Press unit air volume loss is approximately 10%, and the high static pressure unit static pressure loss is around 20%.
Product Features
Available in horizontal surface-mounted, horizontal concealed, vertical surface-mounted, vertical concealed, ceiling-mounted, cabinet-style, wall-mounted, and more series.
Low overall height, saving building space.
High cooling (heating) capacity, low noise, three-speed motor for adjustable air volume, catering to various usage requirements.
The entire unit is made of hot-dipped galvanized steel, copper pipes, and aluminum fins, offering strong rust resistance.
The drip pan is fully molded, and the insulation uses a full-pressure bonding process, eliminating concerns of condensation.
Equipped with exhaust and drain functions, ensuring thorough heat exchange and preventing pipe cracking due to freezing.
The heat exchanger is made of copper tubes and high-efficiency aluminum fins, processed through mechanical expansion.
The unit employs an efficient aluminum finned heat exchanger with a low-noise fan configuration, enhancing heat exchange and maximizing the heat exchanger's thermal transfer efficiency.
Precision design allows for the selection of left or right spiral ordering at will. If required by the customer, an automatic temperature control unit can be provided for constant temperature control of the controlled area; (temperature control unit to be ordered separately)
The motor is an energy-saving fixed phase capacitor motor, equipped with imported high-precision steel ball bearings that are self-lubricating. The motor shafts are all heat-treated and chrome-plated for durability, with easy disassembly at the fixed points. The motor leads are protected by metal hoses, meeting international standards.
The static pressure at the ordinary coiled discharge outlet is 0~12Pa, while the static pressure at the pressure residual discharge outlet is 30Pa (or ≤50Pa), with the code H.
The water tray and insulation are molded, with an overall adhesive bonding process, ensuring durability without weld marks. The design is aesthetically pleasing and lightweight, with no condensation or dripping. The exposed piping is made from sheet metal produced by Baosteel Shanghai, which is surface coated. The concealed piping is made from galvanized steel or fingerprint-resistant steel.
The coiled material is made from seamless copper tubes with corrugated aluminum fins, formed by hydraulic or mechanical expansion. The coil box is lined with sound-absorbing and insulating materials, with the copper tubes arranged in an alternating pattern, offering exceptional heat transfer performance and minimal air resistance.