- AllProduct Category
-
Explosion-proof Electric/Steam/Hot Water Heater Blowers
Humidifier and Dehumidifier in One
Rotary Dehumidification Unit - Customized
Mobile Air Conditioner/Portable Air Cooler
Fan Coil Unit/Air Handling Unit
Smart Dehumidifier Unit
Explosion-proof Modular Air Handling Unit / Swimming Pool Dehumidifying Air Handling Unit
Explosion-Proof Rooftop AC Series
Explosion-Proof Cold Water (Hot Water) Unit Series
Explosion-Proof Oven
Explosion-proof Air curtain Machine
Explosion-proof Temperature and Humidity Control Unit/Non-standard Temperature and Humidity Control System
Industrial Air Conditioning / Explosion-proof Industrial Air Conditioning
Cabinet Air Conditioners / Explosion-Proof Cabinet Air Conditioners
Explosion-proof Fan Coil Unit
Explosion-Proof Refrigerator
Explosion-proof Air Conditioner
Explosion-Proof Dehumidifier
Humidifier/Blast-Proof Humidifier
Dehumidifier


详情描述
The YingTeng FP series fan coil units incorporate advanced technical strengths from similar products domestically and internationally. Compliant with national standards and after numerous trials and measurements, they have efficiently completed a series of technical design improvements. As a result, they offer superior performance, wide applications, a complete range of types, high efficiency, and low noise. The series includes horizontal concealed, horizontal exposed, vertical concealed, vertical exposed, and cassette units. When paired with fresh air handling units, they are widely used in low-noise environments such as hotels, hospitals, office spaces, high-end conference halls, and exhibition halls, making them an ideal terminal device for centralized air conditioning systems.
Product Specifications
Model: FP136 (WM)
Brand: Yingten
Airflow (m³): 1360
Cooling Capacity (W): 7200
Heat (W): 10800
Noise level dB(A): ≤46
Cold Water Supply Temperature: 7℃-12℃
Hot Water Supply Temperature: 40℃-60℃
Working Pressure (KPa): 1.6
Static Pressure: 30Pa/50Pa
Power: 220V/50Hz
Inlet and outlet pipes: ZG3/4
Condensate Drain Pipe: ZG3/4
Dimensions (Length x Width x Height mm): 1415*500*250
Note: The data in the table is the measured value under the test conditions specified in the national standard "Fan Coil Unit" (GB/T19232-2003).
1. Cooling condition parameters: Inlet dry bulb temperature DB = 27°C, wet bulb temperature WB = 19.5°C.
Cold water inlet temperature: 7°C, outlet temperature: 12°C.
Heating operating parameters:进口 air dry bulb temperature DB = 21°C, incoming water temperature 60°C.
2. Noise Measurement: Values measured at 1-meter distances above and below the front of the unit in an anechoic chamber.
3. Standard configuration of vertical concealed units features an outdoor static pressure of 12 Pa.
4. Water resistance refers to the resistance at the rated flow rate; input power refers to the input power at the high airflow setting.
5. When selecting a combination cold and hot twin tube unit, refer to the main technical parameters in the table above. One row of heat is approximately 40% of three rows of heat, low static...
The air volume loss of the pressurizing unit is approximately 10%, and the static pressure loss of the high static pressure unit is about 20%.
Product Features
We offer a range including horizontal surface-mounted, horizontal concealed, vertical surface-mounted, vertical concealed, ceiling-mounted, cabinet-style, wall-mounted, and more.
Low overall height, saving construction space.
High cooling (heating) capacity, low noise, three-speed motor for adjustable air volume, catering to diverse usage requirements.
The whole unit is made of hot-dipped galvanized steel, copper tubes, and aluminum fins, offering strong corrosion resistance.
The drip pan is fully molded, and the insulation is applied using a whole-pressure bonding technique, eliminating concerns about condensation.
Equipped with exhaust and drain functions, ensuring thorough heat exchange and preventing pipe cracking due to freezing.
The cooler uses copper tubes and high-efficiency aluminum fins, mechanically drawn for processing.
The unit features an efficient aluminum finned heat exchanger with a low-noise fan, enhancing heat exchange and maximizing the heat exchanger's thermal transfer efficiency.
精密 design allows for the left and right configurations to be selected at will for ordering. An automatic temperature control unit can be optionally provided for maintaining a constant temperature in the controlled area; (temperature control unit to be ordered separately)
The motor is an energy-saving fixed phase capacitor motor, equipped with imported high-precision ball bearings that are self-lubricating. The motor shafts are all heat-treated and hard-chromium coated for durability, with easy disassembly at the fixed points. The motor leads are protected by metal hoses, meeting international standards.
The static pressure at the common coiled duct outlet is 0~12Pa, while the static pressure at the residual pressure type outlet is 30Pa (or ≤50Pa), with the code H.
The water tray and insulation are molded, with an overall adhesive bonding process, ensuring durability without weld marks, an aesthetically pleasing and lightweight design, no condensation or dripping. The exposed pipe fittings are made from steel sheets produced by Shanghai Baosteel, with a spray-painted surface, while the concealed pipe fittings are made from galvanized steel or fingerprint-resistant steel.
The coiled tube material is made by inserting corrugated aluminum fins into seamless copper tubes, which are then hydraulically or mechanically expanded. The interior of the coil box is lined with sound-absorbing and insulating material, with the copper tubes arranged in an interlaced pattern, offering exceptional thermal conductivity and minimal air resistance.