- AllProduct Category
-
Explosion-proof Electric/Steam/Hot Water Heater Blowers
Humidifier and Dehumidifier in One
Rotary Dehumidification Unit - Customized
Mobile Air Conditioner/Portable Air Cooler
Fan Coil Unit/Air Handling Unit
Smart Dehumidifier Unit
Explosion-proof Modular Air Handling Unit / Swimming Pool Dehumidifying Air Handling Unit
Explosion-Proof Rooftop AC Series
Explosion-Proof Cold Water (Hot Water) Unit Series
Explosion-Proof Oven
Explosion-proof Air curtain Machine
Explosion-proof Temperature and Humidity Control Unit/Non-standard Temperature and Humidity Control System
Industrial Air Conditioning / Explosion-proof Industrial Air Conditioning
Cabinet Air Conditioners / Explosion-Proof Cabinet Air Conditioners
Explosion-proof Fan Coil Unit
Explosion-Proof Refrigerator
Explosion-proof Air Conditioner
Explosion-Proof Dehumidifier
Humidifier/Blast-Proof Humidifier
Dehumidifier


详情描述
The YingTeng FP series fan coil units incorporate advanced technologies from similar products domestically and internationally. In accordance with national standards, after numerous trials and tests, they have efficiently completed a series of technical design improvements, making them superior in performance, versatile in application, comprehensive in variety, high in efficiency, and low in noise. The range includes horizontal concealed, horizontal exposed, vertical concealed, vertical exposed, and cassette unit series. When paired with fresh air handling units, they are widely used in low-noise environments such as hotels, hospitals, office spaces, high-end conference halls, and exhibition halls, serving as ideal terminal units for centralized air conditioning systems.
Product Specifications
Model: FP85 (WM)
Brand: YingTeng
Airflow (m³): 850
Cooling Capacity (W): 4500
Heat (W): 6750
Noise dB(A): ≤43
Cold Water Supply Temperature: 7℃-12℃
Supplying Hot Water Temperature: 40℃-60℃
Working Pressure (KPa): 1.6
Static Pressure: 30 Pa / 50 Pa
Power: 220V/50Hz
In and Out Pipe: ZG3/4
Condensate Drain Pipe: ZG3/4
Dimensions (Length x Width x Height mm): 1080 x 500 x 250
Note: The data in the table is the measured value under the test conditions specified by the national standard for "Fan Coil Units" (GB/T19232-2003).
1. Cooling supply parameters: Inlet dry bulb temperature DB=27°C, wet bulb temperature WB=19.5°C.
Inlet water temperature: 7℃, outlet water temperature: 12℃.
Heating operating parameters:进口 air dry bulb temperature DB = 21°C, incoming water temperature 60°C.
2. Noise Measurement: Values measured at 1 meter distance from the front and above/below the equipment in an anechoic chamber.
3. Standard configuration of vertical concealed units features an outdoor static pressure of 12 Pa.
4. Water resistance refers to the water resistance at the rated flow rate; input power refers to the input power at high airflow.
5. When selecting a combination of cold and hot twin coil units, refer to the main technical parameters in the table above. One row of heat is approximately 40% of three rows of heat, low static...
The air volume loss of the pressuring unit is approximately 10%, and the static pressure loss of the high static pressure unit is about 20%.
Product Features
Vertical exposed, horizontal exposed, vertical concealed, horizontal concealed, ceiling-mounted, cabinet-style, wall-mounted, and more series.
Low overall height, saving building space.
High cooling (heating) capacity, low noise, three-speed motor for adjustable air volume, catering to various usage requirements.
The entire unit is made of hot-dipped galvanized steel, copper tubes, and aluminum fins, offering strong corrosion resistance.
The water pan is fully molded, and the insulation uses an integral pressure bonding process, eliminating concerns about condensation.
Equipped with exhaust and drain functions, ensuring thorough heat exchange and preventing pipe cracking due to freezing.
The heat exchanger is made by mechanical drawing process, using copper tubes and high-efficiency aluminum fins.
The unit features an efficient aluminum finned heat exchanger with a low-noise fan, enhancing heat exchange and maximizing the heat exchanger's thermal transfer efficiency.
精密 design allows for the selection of either left or right-hand coils for ordering. An automatic temperature control unit can be optionally provided for constant temperature control of the controlled area; (temperature control unit to be ordered separately)
The motor is an energy-saving fixed phase capacitor motor, equipped with imported high-precision steel ball bearings that are self-lubricating. The motor shafts are all heat-treated and chrome-plated for durability and easy disassembly at the fixed points. The motor leads are protected by metal hoses, conforming to international standards.
The standard coiled discharge outlet static pressure is 0~12Pa, while the residual pressure discharge outlet static pressure is 30Pa (or ≤50Pa), with the code H.
The water tray and insulation are molded, with an overall adhesive bonding process, ensuring durability without weld marks. The design is aesthetically pleasing and lightweight, with no condensation or dripping. The exposed piping is made from sheets produced by Baosteel Shanghai, which are spray-painted for surface treatment, while the concealed piping is made from galvanized steel or fingerprint-resistant steel.
The coil material is made of seamless copper tubes with corrugated aluminum fins, formed through hydraulic or mechanical expansion. The coil casing is lined with sound-absorbing insulation material, featuring an intricate arrangement of copper tubes, offering superior heat transfer performance and extremely low air resistance.