- AllProduct Category
-
Explosion-proof Electric/Steam/Hot Water Heater Blowers
Humidifier and Dehumidifier in One
Rotary Dehumidification Unit - Customized
Mobile Air Conditioner/Portable Air Cooler
Fan Coil Unit/Air Handling Unit
Smart Dehumidifier Unit
Explosion-proof Modular Air Handling Unit / Swimming Pool Dehumidifying Air Handling Unit
Explosion-Proof Rooftop AC Series
Explosion-Proof Cold Water (Hot Water) Unit Series
Explosion-Proof Oven
Explosion-proof Air curtain Machine
Explosion-proof Temperature and Humidity Control Unit/Non-standard Temperature and Humidity Control System
Industrial Air Conditioning / Explosion-proof Industrial Air Conditioning
Cabinet Air Conditioners / Explosion-Proof Cabinet Air Conditioners
Explosion-proof Fan Coil Unit
Explosion-Proof Refrigerator
Explosion-proof Air Conditioner
Explosion-Proof Dehumidifier
Humidifier/Blast-Proof Humidifier
Dehumidifier


详情描述
The YingTeng FP series fan coil units incorporate advanced technologies from both domestic and international counterparts. Compliant with national standards and after numerous trials and tests, they have achieved a series of technical design improvements with high efficiency. As a result, they offer superior performance, wide applications, a complete range of types, high efficiency, and low noise. The series includes horizontal concealed, horizontal exposed, vertical concealed, vertical exposed, and cassette units. When paired with fresh air handling units, they are extensively used in low-noise environments such as hotels, hospitals, office spaces, high-end conference halls, and exhibition halls, making them an ideal terminal device for centralized air conditioning systems.
Product Specifications
Model: FP102 (WA)
Brand: YingTeng
Airflow (m³): 1020
Cooling Capacity (W): 5400
Heat (W): 8100
Noise dB(A): ≤45
Cold Water Supply Temperature: 7℃-12℃
Supplying Hot Water Temperature: 40℃-60℃
Working Pressure (KPa): 1.6
Static Pressure: 30Pa/50Pa
Power Supply: 220V/50Hz
In-and-out water pipes: ZG3/4
Condensate Drain Pipe: ZG3/4
Dimensions (Length x Width x Height mm): 1440 x 475 x 246
Note: The data in the table is the measured value under the test conditions specified by the national standard for "Fan Coil Units" (GB/T19232-2003).
1. Supply cooling operating parameters: inlet dry bulb temperature DB = 27°C, wet bulb temperature WB = 19.5°C.
Cold water inlet temperature: 7℃, outlet temperature: 12℃.
Heating operating parameters: Imported air dry bulb temperature DB = 21°C, incoming water temperature 60°C.
2. Noise Measurement: Values measured at 1 meter in front of and above the equipment in an anechoic chamber.
3. Standard configuration of the vertical concealed unit features an outdoor static pressure of 12 Pa.
4. Water resistance refers to the water resistance at the rated flow rate; input power refers to the input power at high airflow.
5. When selecting a combination cold and hot twin coil unit, refer to the main technical parameters in the table above. One row of heat is approximately 40% of three rows of heat, low static...
Airflow loss in pressurizing units is approximately 10%, while static pressure loss in high static pressure units is about 20%.
Product Features
Available in horizontal surface-mounted, horizontal concealed, vertical surface-mounted, vertical concealed, ceiling-mounted, cabinet-style, wall-mounted, and more series.
Low overall height, saving building space.
High cooling (heating) capacity, low noise, three-speed motor for adjustable air volume, catering to various usage requirements.
The complete unit is made of hot-dipped galvanized steel, copper tubes, and aluminum fins, offering strong rust resistance.
The overall die-cast drip pan, with overall pressure bonding technology for insulation, ensures no condensation water issues.
Equipped with exhaust and drain functions, ensuring thorough heat exchange and preventing pipeline cracking due to freezing.
The condenser is made by mechanical bending of copper tubes and high-efficiency aluminum fins.
The unit is equipped with high-efficiency aluminum finned heat exchangers and low-noise fans, enhancing heat exchange and maximizing the heat exchanger's thermal transfer efficiency.
Precision design allows for the selection of either left or right-hand coils for ordering. If required by the customer, an automatic temperature control unit can be provided for constant temperature control of the controlled area; (temperature control unit to be ordered separately)
The motor is an energy-saving fixed-phase capacitor motor, equipped with imported high-precision ball bearings that are self-lubricating. The motor shafts are all heat-treated and chrome-plated for durability, with ease of disassembly at the fixed points. The motor leads are protected by metal hoses, meeting international standards.
The standard coiled air outlet static pressure is 0~12Pa, while the residual pressure type air outlet static pressure is 30Pa (or ≤50Pa), with the code H.
The water tray and insulation are molded, with an overall adhesive bonding process, ensuring strength, durability without weld marks, and an aesthetically pleasing, lightweight design; no condensation or dripping. The exposed piping is made from sheets produced by Shanghai Baogang, with a spray-painted surface, while the concealed piping is made from galvanized steel or fingerprint-resistant steel plates.
The coiled material is made of seamless copper tubes with corrugated aluminum fins, formed through hydraulic or mechanical expansion. The coil box is lined with sound-absorbing and insulating material, featuring copper tubes in an interlaced arrangement, offering exceptional heat transfer performance and low air resistance.