- AllProduct Category
-
Explosion-proof Electric/Steam/Hot Water Heater Blowers
Humidifier and Dehumidifier in One
Rotary Dehumidification Unit - Customized
Mobile Air Conditioner/Portable Air Cooler
Fan Coil Unit/Air Handling Unit
Smart Dehumidifier Unit
Explosion-proof Modular Air Handling Unit / Swimming Pool Dehumidifying Air Handling Unit
Explosion-Proof Rooftop AC Series
Explosion-Proof Cold Water (Hot Water) Unit Series
Explosion-Proof Oven
Explosion-proof Air curtain Machine
Explosion-proof Temperature and Humidity Control Unit/Non-standard Temperature and Humidity Control System
Industrial Air Conditioning / Explosion-proof Industrial Air Conditioning
Cabinet Air Conditioners / Explosion-Proof Cabinet Air Conditioners
Explosion-proof Fan Coil Unit
Explosion-Proof Refrigerator
Explosion-proof Air Conditioner
Explosion-Proof Dehumidifier
Humidifier/Blast-Proof Humidifier
Dehumidifier


详情描述
The Yinteng FP series fan coil units incorporate advanced technologies from both domestic and international counterparts. In accordance with national standards, after numerous trials and tests, they have achieved a series of technical design improvements with high efficiency. As a result, they offer superior performance, wide applications, a complete range of types, high efficiency, and low noise. The series includes horizontal concealed, horizontal exposed, vertical concealed, vertical exposed, and card-mounted units. When paired with fresh air handling units, they are extensively used in low-noise environments such as hotels, hospitals, office spaces, high-end conference halls, and exhibition halls, making them an ideal terminal device for centralized air conditioning systems.
Product Specifications
Model: FP136 (LG)
Brand: YingTeng
Airflow (m³): 1360
Cooling Capacity (W): 7200
Heat (W): 10800
Noise db(A): ≤46
Cold Water Supply Temperature: 7℃-12℃
Hot Water Supply Temperature: 40℃-60℃
Working Pressure (KPa): 1.6
Static Pressure: 30Pa/50Pa
Power: 220V/50Hz
Inlet and outlet pipes: ZG3/4
Condensate Drain Pipe: ZG3/4
Dimensions (Length x Width x Height mm): 530 x 285 x 1750
Note: The data in the table is the measured value under the test conditions specified in the national standard "Fan Coil Unit" (GB/T 19232-2003).
1. Cooling conditions parameters: Inlet dry bulb temperature DB = 27℃, wet bulb temperature WB = 19.5℃.
Inlet water temperature at 7°C, outlet water temperature at 12°C.
Heating operation parameters: Imported dry bulb air temperature DB = 21°C, incoming water temperature 60°C.
2. Noise Measurement: Values measured at 1 meter in front of and above the equipment in an anechoic chamber.
3. Standard configuration of vertical concealed units features an outdoor static pressure of 12 Pa.
4. Water resistance refers to the resistance at the rated flow rate; input power refers to the input power at high airflow.
5. When selecting a combination cold and hot twin coil unit, refer to the main technical parameters in the table above. One row of heat is approximately 40% of three rows of heat, low static...
Airflow loss in pressurizing units is approximately 10%, and static pressure loss in high-pressure units is about 20%.
Product Features
Available in horizontal surface-mounted, horizontal concealed, vertical surface-mounted, vertical concealed, ceiling-mounted, cabinet-style, wall-mounted, and other series.
Low overall height, saving building space.
High cooling (heating) capacity, low noise, three-speed motor for adjustable air volume, meets various usage requirements.
The complete unit is made of hot-dip galvanized sheet, copper pipes, and aluminum fins, offering strong corrosion resistance.
The drip pan is fully molded for a seamless design, and the insulation is bonded using a unified pressing technique, eliminating concerns of condensation.
Equipped with exhaust and draining functions, ensures adequate heat exchange and prevents pipeline cracking from freezing.
The evaporator is made by mechanical expansion of copper tubes and high-efficiency aluminum fins.
The unit employs an efficient aluminum finned heat exchanger with a low-noise fan configuration, enhancing heat exchange and maximizing the heat exchanger's thermal transfer efficiency.
Precision design allows for the left and right configurations of the coils to be selected at will for ordering. If required by the customer, an automatic temperature control unit can be provided for constant temperature control of the controlled area; (temperature control unit to be ordered separately)
The motor is an energy-saving fixed phase capacitor motor, equipped with imported high-precision steel ball bearings that can be self-lubricated. The motor shafts are all tempered and treated with hard chrome, ensuring durability and ease of disassembly at the fixed points. The motor leads are protected with metal hoses, compliant with international standards.
The static pressure at the common coiled discharge outlet is 0~12Pa, while the static pressure at the pressure surplus discharge outlet is 30Pa (or ≤50Pa), with the code H.
The water tray and insulation are molded, with an overall adhesive bonding process, ensuring durability without weld marks, with an aesthetically pleasing and lightweight design, no condensation or dripping; the exposed piping is made from steel plates produced by Baosteel Shanghai, with a spray-painted surface, while the concealed piping is made from galvanized steel or fingerprint-resistant steel plates.
The coil material is made of seamless copper tubes with corrugated aluminum fins, formed through hydraulic or mechanical expansion. The coil casing is lined with sound-absorbing insulation material, featuring an intricate arrangement of copper tubes that offers excellent heat transfer performance and minimal air resistance.