The YingTeng FP series fan coil units incorporate advanced technologies from both domestic and international counterparts. In accordance with national standards, after numerous trials and measurements, a series of technical design improvements have been efficiently implemented, resulting in superior performance, wide applications, a complete range of types, high efficiency, and low noise. The series includes horizontal concealed, horizontal exposed, vertical concealed, vertical exposed, and cassette units. When paired with fresh air handling units, they are extensively used in low-noise environments such as hotels, hospitals, office spaces, high-end conference halls, and exhibition halls, making them an ideal terminal device for centralized air conditioning systems.

Product Specifications

Model: FP170 (KC)

Brand: YingTeng

Airflow (m³): 1700

Cooling Capacity (W): 9000

Heat (W): 13,500

Noise dB(A): ≤48

Cold Water Supply Temperature: 7℃-12℃

Hot Water Supply Temperature: 40℃-60℃

Working Pressure (KPa): 1.6

Static Pressure: 30Pa/50Pa

Power: 220V/50Hz

Inlet and outlet pipes: ZG3/4

Condensate Drain Pipe: ZG3/4

Dimensions (Length x Width x Height mm): 980 x 980 x 390

Note: The data in the table is the measured value under the test conditions specified by the national standard for "Fan Coil Units" (GB/T19232-2003).

1. Cooling supply parameters: Inlet dry bulb temperature DB=27℃, wet bulb temperature WB=19.5℃.

Cold water inlet temperature: 7℃, outlet temperature: 12℃.

Heating operating parameters:进口 air dry bulb temperature DB = 21°C, incoming water temperature 60°C.

2. Noise Measurement: Values measured at 1 meter distance from the front and above/below the equipment in an anechoic chamber.

3. The standard configuration of the vertical concealed unit features an outdoor static pressure of 12 Pa.

4. Water resistance refers to the water resistance at the rated flow rate; input power refers to the input power at high airflow.

5. When selecting a combination cold and hot twin coil unit, refer to the main technical parameters in the table above. One row of heat is approximately 40% of three rows of heat, low static...

Airflow loss in pressurizing units is approximately 10%, while static pressure loss in high-pressure units is about 20%.

Product Features

Available in horizontal surface-mounted, horizontal concealed, vertical surface-mounted, vertical concealed, ceiling-mounted, cabinet-style, wall-mounted, and other series.

Low overall height, saving building space.

High cooling (heating) capacity, low noise, three-speed motor for adjustable air volume, meets various usage requirements.

The complete unit is made of hot-dipped galvanized sheet, copper tubes, and aluminum fins, offering strong rust prevention.

The water collection pan is fully molded, with overall pressure bonding technology for insulation, eliminating worries about condensation water.

Equipped with exhaust and drain functions, ensuring thorough heat exchange and preventing pipe cracking due to freezing.

The condenser is made by mechanical bending of copper tubes and high-efficiency aluminum fins.

The unit features an efficient aluminum finned heat exchanger with a low-noise fan configuration, enhancing heat exchange and maximizing the heat exchanger's thermal transfer efficiency.

精密 design allows for the left and right configurations to be freely selected for ordering. If required by the customer, an automatic temperature control unit can be optionally provided for constant temperature control of the controlled space; (temperature control unit to be ordered separately)

The motor is an energy-saving fixed phase capacitor motor, equipped with imported high-precision ball bearings that can be self-lubricated. The motor shafts are all heat treated and chrome-plated for durability and easy disassembly at the fixed points. The motor leads are protected with metal hoses, meeting international standards.

Standard coiled duct outlet static pressure is 0~12Pa, while the residual pressure type outlet static pressure is 30Pa (or ≤50Pa), with the code H.

The water tray and insulation are molded, with an overall adhesive bonding process, ensuring solid durability without weld marks. The design is aesthetically pleasing and lightweight, with no condensation or dripping. The exposed piping is made from sheets produced by Baosteel Shanghai, which are surface-coated. The concealed piping is made from galvanized steel or fingerprint-resistant steel.

The coiled material is made from seamless copper tubes with corrugated aluminum fins, formed by hydraulic or mechanical expansion. The coil box is lined with sound-absorbing and insulating materials, featuring copper tubes arranged in an interlaced pattern, offering exceptional heat transfer performance and minimal air resistance.