- AllProduct Category
-
Explosion-proof Electric/Steam/Hot Water Heater Blowers
Humidifier and Dehumidifier in One
Rotary Dehumidification Unit - Customized
Mobile Air Conditioner/Portable Air Cooler
Fan Coil Unit/Air Handling Unit
Smart Dehumidifier Unit
Explosion-proof Modular Air Handling Unit / Swimming Pool Dehumidifying Air Handling Unit
Explosion-Proof Rooftop AC Series
Explosion-Proof Cold Water (Hot Water) Unit Series
Explosion-Proof Oven
Explosion-proof Air curtain Machine
Explosion-proof Temperature and Humidity Control Unit/Non-standard Temperature and Humidity Control System
Industrial Air Conditioning / Explosion-proof Industrial Air Conditioning
Cabinet Air Conditioners / Explosion-Proof Cabinet Air Conditioners
Explosion-proof Fan Coil Unit
Explosion-Proof Refrigerator
Explosion-proof Air Conditioner
Explosion-Proof Dehumidifier
Humidifier/Blast-Proof Humidifier
Dehumidifier


详情描述
The YingTeng FP series fan coil units incorporate advanced technology from similar products both domestically and internationally. In compliance with national standards, after numerous trials and tests, they have achieved a series of technical design improvements with high efficiency. Thus, they offer superior performance, wide applications, a complete range of types, high efficiency, and low noise. The series includes horizontal concealed, horizontal exposed, vertical concealed, vertical exposed, and cassette units. When paired with air handling units, they are extensively used in low-noise environments such as hotels, hospitals, office spaces, high-end conference halls, and exhibition halls, making them an ideal terminal unit for centralized air conditioning systems.
Product Specifications
Model: FP85 (KC)
Brand: YingTeng
Airflow (m³): 850
Cooling Capacity (W): 4500
Heat (W): 6750
Noise db(A): ≤43
Cold Water Supply Temperature: 7℃-12℃
Supplying Hot Water Temperature: 40℃-60℃
Working Pressure (KPa): 1.6
Static Pressure: 30Pa/50Pa
Power: 220V/50Hz
In and Out Pipe: ZG3/4
Condensate Drain Pipe: ZG3/4
Dimensions (Length x Width x Height mm): 830 x 830 x 390
Note: The data in the table are the measured values under the test conditions specified by the national standard "Fan Coils Unit" (GB/T19232-2003).
1. Cooling operation parameters: Inlet dry bulb temperature DB = 27°C, wet bulb temperature WB = 19.5°C.
Inlet water temperature for cold water: 7°C, outlet water temperature: 12°C.
Heating operating parameters: Inlet air dry bulb temperature DB = 21°C, incoming water temperature 60°C.
2. Noise Measurement: Values measured at 1 meter forward and above/below the unit in the anechoic chamber.
3. The standard configuration of the vertical concealed unit has an outdoor static pressure of 12 Pa.
4. Water resistance refers to the water resistance at the rated flow rate; input power refers to the input power at high airflow.
5. When selecting a combined cold and hot twin tube unit, refer to the main technical parameters in the table above. One row of heat is approximately 40% of three rows of heat, low static...
The air volume loss of the press unit is approximately 10%, and the static pressure loss of the high static pressure unit is about 20%.
Product Features
There are series including horizontal exposed, horizontal concealed, vertical exposed, vertical concealed, ceiling-mounted, cabinet-style, wall-mounted, and more.
Low overall height, saving architectural space.
High cooling (heating) capacity, low noise, three-speed motor for adjustable air volume, meets various usage requirements.
The complete unit is made of hot-dipped galvanized steel, copper pipes, and aluminum fins, offering strong rust prevention capabilities.
The water pan is fully molded, and the insulation uses a whole-pressure bonding technique, eliminating concerns of condensation.
Equipped with exhaust and drain functions, ensuring thorough heat exchange and preventing pipeline cracking due to freezing.
The evaporator is made of copper tubes and high-efficiency aluminum fins, mechanically expanded.
The unit features an efficient aluminum finned heat exchanger with a low-noise fan, enhancing heat exchange and maximizing the heat exchanger's thermal transfer efficiency.
精密 design allows for the left and right configurations to be selected at will for ordering. An automatic temperature control unit can be optionally provided for constant temperature control of the controlled area; (temperature control unit to be ordered separately)
The motor is an energy-saving fixed-phase capacitor motor, equipped with imported high-precision steel ball bearings that are self-lubricating. The motor shafts are all heat-treated and treated with hard chrome for durability, making them easy to disassemble and assemble at the fixed points. The motor leads are protected with metal hoses, compliant with international standards.
Standard coil outlet static pressure is 0~12Pa, while the residual pressure outlet static pressure is 30Pa (or ≤50Pa), with the code H.
The water pan and insulation are molded, with an overall adhesive bonding process, ensuring durability without weld marks. The design is aesthetically pleasing and lightweight, with no condensation or dripping. The exposed piping is made from steel plates produced by Baosteel Shanghai, which are spray-painted for surface treatment, while the concealed piping is made from galvanized steel or fingerprint-resistant steel.
The coiled material is made from seamless copper tubes with corrugated aluminum fins, formed by hydraulic or mechanical expansion. The coil housing is lined with sound-absorbing and insulating materials, featuring copper tubes arranged in an interlaced pattern, offering exceptional heat transfer performance and minimal air resistance.