- AllProduct Category
-
Explosion-proof Electric/Steam/Hot Water Heater Blowers
Humidifier and Dehumidifier in One
Rotary Dehumidification Unit - Customized
Mobile Air Conditioner/Portable Air Cooler
Fan Coil Unit/Air Handling Unit
Smart Dehumidifier Unit
Explosion-proof Modular Air Handling Unit / Swimming Pool Dehumidifying Air Handling Unit
Explosion-Proof Rooftop AC Series
Explosion-Proof Cold Water (Hot Water) Unit Series
Explosion-Proof Oven
Explosion-proof Air curtain Machine
Explosion-proof Temperature and Humidity Control Unit/Non-standard Temperature and Humidity Control System
Industrial Air Conditioning / Explosion-proof Industrial Air Conditioning
Cabinet Air Conditioners / Explosion-Proof Cabinet Air Conditioners
Explosion-proof Fan Coil Unit
Explosion-Proof Refrigerator
Explosion-proof Air Conditioner
Explosion-Proof Dehumidifier
Humidifier/Blast-Proof Humidifier
Dehumidifier


详情描述
The YingTeng FP series fan coil units incorporate advanced technology from similar products both domestically and internationally. In accordance with national standards, after numerous trials and measurements, a series of technical design improvements have been efficiently implemented, resulting in superior performance, wide applications, a complete range of types, high efficiency, and low noise. The series includes horizontal concealed, horizontal exposed, vertical concealed, vertical exposed, and cassette units. When paired with air handling units, they are extensively used in low-noise environments such as hotels, hospitals, office spaces, high-end conference halls, and exhibition halls, making them an ideal terminal device for centralized air conditioning systems.
Product Specifications
Model: FP238 (KC)
Brand: YingTeng
Airflow (m³): 2380
Cooling Capacity (W): 12,600
Heat (W): 18900
Noise db(A): ≤52
Cool Water Supply Temperature: 7℃-12℃
Supplying Hot Water Temperature: 40℃-60℃
Working Pressure (KPa): 1.6
Static Pressure: 30Pa/50Pa
Power: 220V/50Hz
Inlet and outlet pipes: ZG3/4
Condensate Drain Pipe: ZG3/4
Dimensions (Length x Width x Height, mm): 980 x 980 x 390
Note: The data in the table is the measured value under the test conditions specified in the national standard "Fan Coil Unit" (GB/T19232-2003).
1. Cooling supply conditions parameters: Inlet dry bulb temperature DB = 27°C, wet bulb temperature WB = 19.5°C.
Cold water inlet temperature: 7°C, outlet temperature: 12°C.
Heating工况parameters: Inlet air dry bulb temperature DB=21℃, inlet water temperature 60℃.
2. Noise Measurement: Values measured at 1 meter in front of and above the equipment in an anechoic chamber.
3. The standard configuration of the vertical concealed unit features an outdoor static pressure of 12 Pa.
4. Water resistance refers to the water resistance at the rated flow rate; input power refers to the input power at high airflow.
5. When selecting a combination cold and hot twin coil unit, refer to the main technical parameters in the table above. One row of heat is approximately 40% of three rows of heat, low static...
The air volume loss of the press unit is approximately 10%, while the static pressure loss of the high-pressure unit is about 20%.
Product Features
Available in horizontal surface-mounted, horizontal concealed, vertical surface-mounted, vertical concealed, ceiling-mounted, cabinet-style, wall-mounted, and more series.
Low overall height, saving construction space.
High cooling (heating) capacity, low noise, three-speed motor for adjustable air volume, catering to various usage requirements.
The entire unit is made of hot-dipped galvanized steel, copper pipes, and aluminum fins, offering strong rust resistance.
The drip pan is fully molded, and the insulation is applied using a whole-pressure bonding technique, eliminating concerns about condensation.
Equipped with exhaust and drain functions, ensuring thorough heat exchange and preventing pipe cracking due to freezing.
The condenser is made by mechanical bending of copper tubes and high-efficiency aluminum fins.
The unit employs an efficient aluminum finned heat exchanger with a low-noise fan, enhancing heat exchange and maximizing the heat exchanger's thermal transfer efficiency.
Precision design allows for the selection of either left or right coils for ordering. If required by the customer, an automatic temperature control unit can be provided for constant temperature control of the controlled area; (temperature control unit to be ordered separately)
The motor is a energy-saving fixed phase capacitor motor, equipped with imported high-precision ball bearings that are self-lubricating. The motor shafts are all treated with quenching and hard chrome, ensuring durability and easy disassembly at fixed points. The motor leads are protected by metal flexible hoses, meeting international standards.
Standard coil outlet air pressure is 0~12Pa, pressure retaining outlet air pressure is 30Pa (or ≤50Pa), with the code H.
The water tray and insulation are molded, with an overall adhesive bonding process, ensuring durability without weld marks. The appearance is beautiful and lightweight, with no condensation or dripping. The exposed piping is made from sheets produced by Baosteel Shanghai, which are spray-painted for the surface finish. The concealed piping is made from galvanized steel or fingerprint-resistant steel plates.
The coiled material is made from seamless copper tubes with corrugated aluminum fins, formed by hydraulic or mechanical expansion. The coil box is lined with sound-absorbing and insulating materials, with the copper tubes arranged in an interlaced pattern, offering exceptional heat transfer performance and low air resistance.