详情描述

Yinteng High-Temperature Explosion-Proof Cabinet Air Conditioner

Product Specifications

Model: BKG-50-Ex1500G

Brand: YingTeng

Cooling Capacity: 1500W

Interior temperature range: 25℃~38℃

Exterior Temperature Range: -5℃ to 55℃

System Pressure Rating: 26 bar

Power: 220V/50Hz

Operating Current: 3.3A

Input Power: 750W

Cabinet air circulation volume: 270 m³/h

Cabinet external air volume: 860 m³/h

Internal Protection Rating: IP54

External Protection Rating: IP34

Noise: 65 dB(A)

Weight: 38 kg

Dimensions (width x height x depth): 370*875*240mm

Explosion-proof Mark: Ex db ib mb IIB T4 Gb/Ex db eb ib mb ll C T4 Gb


Manufacturer: Henan Tongteng Explosion-proof Electrical Appliances Co., Ltd.

Note: The above technical specifications are for reference only; the physical unit shall prevail.

The test operating conditions are: dry bulb temperature of 35℃ inside the electrical cabinet, wet bulb temperature of 26℃ inside the electrical cabinet, and dry bulb temperature of 35℃ outside the electrical cabinet.

2. The above product specifications are for the standard model. For larger cooling capacity or customized products, please call our company for more details.

Inten explosion-proof cabinet air conditioner has explosion-proof markings: Ex db ib mb IIB T4 Gb/Ex db eb ib mb ll C T4 Gb

The Aiting explosion-proof cabinet air conditioner product series complies with the following standards:

GB/T 3836.1 - 2021 "Explosive Atmospheres *1 Part: Equipment General Requirements"

GB/T 3836.2-2021 "Explosive Atmospheres *Part 2: Equipment protected by隔爆外壳 'd'"

GB/T 3836.4-2021 "Explosive Atmospheres *Part 4: Equipment protected by intrinsic safety "i""

GB/T 3836.9-2021 "Explosive Atmospheres *Part 9: Equipment protected by "m" type enclosures"

GB/T 3836.15-2017 "Explosive Atmospheres - Part 15: Design, Selection, and Installation of Electrical Equipment"

The Yinteng explosion-proof cabinet air conditioner operates normally under the following environmental conditions:

a) Altitude not exceeding 2,000m.

b) Suitable for environments with temperatures ranging from -7℃ to 43℃, free of corrosive gases.

c) There are explosive hazard areas formed by mixtures of flammable gases, vapors, and air from Groups II A, II B, T1 to T4.

The "YingTeng" explosion-proof cabinet air conditioner series has been processed with special explosion-proof technology and is suitable for use in flammable and explosive areas in Zones 1 and 2. It is widely applicable in scientific research, oil, chemical, pharmaceutical, and power plant environments where II A, II B, T1 to T4 groups of combustible gases, steam, and air mixtures may form explosive hazards. Explosion-proof cabinet air conditioners are ideal for locations with temperature requirements. The YingTeng explosion-proof cabinet air conditioners have passed inspections by the National Supervision and Inspection Center for Explosion-Proof Electrical Product Quality and have been issued with explosion-proof certification and CCC certification. They feature an aesthetically pleasing design, reasonable structure, and are easy to install and maintain. The entire series employs brand-name compressors, microcomputer intelligent control, digital display, and boasts low noise, stable performance, simple operation, and safety. These units are highly favored in the market. (Customizable options include explosion-proof window air conditioners, explosion-proof duct air conditioners, explosion-proof ceiling air conditioners, explosion-proof fresh air air conditioners, explosion-proof marine air conditioners, explosion-proof corrosion-resistant air conditioners, explosion-proof high-temperature air conditioners, explosion-proof cold storage air conditioners, explosion-proof modular air conditioners, and explosion-proof multi-split air conditioners, etc.).

Inten Explosion-Proof Cabinet Air Conditioner Product Features

Equipped with temperature control and dehumidification functions to ensure ideal temperature and humidity requirements within the electrical control cabinet.

Utilizing high-efficiency spiral rotor compressors, offering high reliability, low energy consumption, and stable quality.

No air heat exchange occurs between the cabinet air and the ambient air, ensuring the internal air of the electrical cabinet remains clean.

Choose high-volume, high-static-pressure centrifugal fans for better air circulation and heat exchange efficiency.

Reasonable air intake and exhaust structure to avoid short-circuiting of air circulation inside the cabinet.

The full touch screen controller can feature alarm capabilities, dehumidification functions, and real-time monitoring of the air conditioner's operating status.

Compact, lightweight, and extremely easy to install, use, and maintain.

Inten Explosion-proof Cabinet Air Conditioner Application Range

Now widely used in machine tools, data processing, communication, finance, metallurgy, petrochemicals, building materials, and automotive industries, some large-scale data processing centers and CNC machining centers in China are also widely employed. The exceptional efficiency and superior performance of the electrical cabinet air conditioners are gradually gaining recognition and usage from an increasing number of high-end customers both domestically and internationally.

Selection Example

The control cabinet has a surface area of 8㎡ (A=8㎡), with an ambient temperature of 35°C (T0=35°C). The total heat generated inside the cabinet is 150W. To maintain an internal cabinet temperature of 28°C, the calculation method for selecting the electrical cabinet air conditioner is as follows:

△T=T0-Ti=35-28=7°C

Qr=5.5xAx△T=5.5x8x7=308W

Qt=1.2x(Qr+Qi)=1.2x(150+308)=458W

Select the air conditioner model BKG-50-Ex600C.