Computer cables are electrical equipment cables, suitable for electronic computers and automated instruments with high requirements for anti-interference at rated voltages of 500V or below. Depending on the specific environmental and usage requirements of the equipment, the cable insulation can be made from materials such as polyethylene, polyvinyl chloride, cross-linked polyethylene, fluoro plastics, and silicone rubber.

Each pair of twisted sheathes and between twisted sheathes and the overall sheath should be uninterrupted.

The cores of the cables should withstand a non-penetration under an alternating voltage of 2000V for 1 minute or 1500V for 5 minutes at 50Hz, as well as between cores and between cores and the shielding or other metallic layers.

High insulation resistance and excellent voltage resistance of polyethylene, along with a small dielectric constant and minimal temperature and frequency-dependent dielectric loss, not only meet transmission performance requirements but also ensure the cable's service life.

To minimize mutual interference between loops and external interference, the cables must be constructed with a shielding structure. The shielding materials include tin-plated or untinned copper wire, copper strip, copper-plastic composite tape, and aluminum-plastic composite tape, among others. The metallic strips are produced by wrapping, with an overlap rate typically not less than 15%. However, specific standards may have special provisions, such as TICW/06, which requires the overlap rate of the shielding metallic strip to be not less than 25%. The metallic wire is produced by braiding, with a braiding coverage rate not less than 80%, and for higher interference resistance requirements, the coverage rate may not be less than 90%.

The shielding requirements for cables are individually adopted for different scenarios: segmented shielding (only for twisted pairs, with each twisted pair having its own shielding), overall shielding (the cable has a single overall shielding layer after the cores are stranded), and segmented + overall shielding (combining both structures). To meet higher requirements of users and usage scenarios, the overall shielding structure can be implemented using a composite shielding method, which includes two layers of shielding, consisting of metallic tape wrapping + metal wire braiding.

Note: If the cable has a segmented shielding structure, the shielding layers should have good insulation properties, and polyester tape or other non-absorbent wrapping tape should be applied on the outer side of the segmented shielding.

Name Edit Voice

DJYPV

Polyethylene insulated twisted copper wire braid shielded with PVC sheath

Electrical Cable Sleeves Count

Install indoor, cable trench, pipeline, etc., with static shielding requirements

Occasion

DJYVP

Polyethylene insulated twisted copper wire braid, overall shielded with PVC sheath

Electrical Cable Sleeves Count

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Occasion

DJYPVP

Polyethylene insulated twisted copper wire, braid shielded and overall shielded

Chlorinated Polyvinyl Chloride (PVC) sheathed computer cable

Install indoor, cable trenches, pipelines, etc., requiring electrostatic shielding

Occasion

DJYP2V

PVC-jacketed shielded copper braided tinned polyethylene insulated wire

Electrical Cable

Install indoor, cable trench, pipeline, etc., with static shielding requirements

Occasion

DJYVP2

Polyethylene insulated twisted copper strip, overall shielded with PVC sheath

Electrical Cable

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Occasion

DJYP2VP2

Polyethylene insulated twisted copper strips, both individually shielded and overall shielded polyvinyl chloride

Enwrap computer cable

Install indoor, cable trench, pipeline, etc., with static shielding requirements

Occasion

DJYP3V

Polyethylene insulated, twisted aluminum-plastic composite tape, shielded with polyvinyl chloride

Computer Cable Jacket

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Event

DJYVP3

Polyethylene insulated twisted aluminum-plastic composite tape, overall shielded with polyvinyl chloride

Computer cable sleeve

Install indoor, cable trenches, pipelines, etc., with static shielding requirements

Occasion

DJYP3VP3

Polyethylene insulated twisted aluminum-plastic composite tape with both shielded and total shielded versions

PVC jacket computer cable

Install indoor, cable trench, pipeline, etc., with static shielding requirements

Occasion

DJYPVR

Polyethylene insulated twisted copper wire braid shielded with PVC sheath

Computer Cable Jacket Soft

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Occasion

DJYVPR

Polyethylene insulated twisted copper wire braided overall shield with PVC sheath

Computer cable sleeve

Install indoor, cable trench, pipeline, etc., with static shielding requirements

Occasion

DJYPVPR

PVC insulated twisted copper wire braid with individual and overall shielding

Polyvinyl Chloride (PVC) sheathed soft computer cable

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Occasion

DJYP2VR

Polyethylene insulated twisted copper tape, shielded with PVC sheath, soft

Computer Cable

Lay indoor, cable trench, pipeline, etc., with static shielding requirements

Occasion

DJYVP2R

Polyethylene insulated twisted copper tape, overall shielded with PVC sheath, soft

Computer Cable

Install indoor, cable trenches, pipelines, etc., with static shielding requirements

Occasion

DJYP2VP2R

Polyethylene insulated twisted copper tape, both with individual shielding and overall shielding polyvinyl chloride.

Thermally protected soft computer cable

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Occasion

DJYP3VR

Polyethylene insulated, twisted pair of aluminum-plastic composite tape, shielded with polyvinyl chloride

Protective Soft Computer Cable

Install indoor, cable trench, pipeline, etc., with static shielding requirements

Occasion

DJYVP3R

Polyethylene insulated, twisted pair aluminum-plastic composite tape, overall shielded polyvinyl chloride

Computer cable sleeve

Lay indoor, cable trenches, pipelines, etc., with static shielding requirements

Occasion

DJYP3VP3R

Polyethylene insulated twisted aluminum-plastic composite tape, with both individual shielding and overall shielding

PVC jacketed soft computer cable

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Occasion

DJYPV22

PVC jacketed, braided shielded copper twisted pair with polyethylene insulation

Steel-braided jacketed computer cable

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Large mechanical external force fixed sites and withstand

DJYVP22

Polyethylene insulated twisted copper wire braid overall shielded with PVC sheath

Steel-braided computer cable

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Large mechanical external force fixed sites and withstand

DJYPVP22

Polyethylene insulated twisted copper wire with both individual and overall shielding

Chlorinated Polyvinyl Chloride (PVC) sheathed steel wire armored computer cable

Install indoor, cable trench, pipeline, etc., with static shielding requirements

Large mechanical external force fixed sites and withstand

DJYP2V22

Polyethylene insulated twisted copper strip, shielded with PVC sheath and steel wire

Computer cable with armor

Lay indoor, cable trenches, pipelines, etc., requiring electrostatic shielding

Large mechanical external force fixation sites and withstand

DJYVP2-22

Polyethylene insulated, twisted copper strip, overall shielded with PVC jacket, steel

Computer cable with armor

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Large mechanical force fixed sites and withstand

DJYP2VP2-22

Polyethylene insulated twisted copper tape, both individually shielded and overall shielded polyvinyl chloride

Thermally protected steel tape armored computer cable

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Large mechanical force fixed site and withstand

DJYP3V22

Polyethylene insulated twisted aluminum-plastic composite tape with shielding polyvinyl chloride

Computer Cable with Steel Tape Armor

Lay indoor, cable trench, pipeline, etc., requiring electrostatic shielding

Large mechanical external force fixation sites and withstand

DJYVP3-22

Polyethylene insulated, twisted aluminum-plastic composite tape, overall shielded with polyvinyl chloride

Computer Cable with Steel Tape Armor Sheath

Lay indoor, cable trench, pipeline, etc., with static shielding requirements

Large mechanical external force fixation sites and withstand

DJYP3VP3-22

Polyethylene insulated twisted aluminum-plastic composite tape with both shielded and total shielded types

PVC sheathed steel tape armored computer cable

Install static shielding for indoor environments, cable trenches, pipelines, etc.

Large machinery with external force fixation and bearing capacity