详情描述
BWDK-3207Y-220(E) Dry-Type Transformer Temperature Control Box
Hunan Changsha Liangwei Electrical Co., Ltd.
BWDK-3207Y-220(E)
BWDK-3207Y-220(E) Button operation method
Step Sudden
| Button operation
| Phase Monitor
| Data Monitor
| Description
| Note
|
1
| Setup Key
| E
| -000
| Enter Password Setting State
|
|
2
| Shift key Or add key
| E
| -232
| Press the shift key or the plus key to enter the password 232
| Incorrect password; the following actions will not write data.
|
3
| Set Key
| 1
| -080
| Set the fan heater temperature value; press the shift key or the increase key to modify this data.
| 80 is the factory-set value, with a range of 50-100.
|
4
| Set Key
| 2
| -100 (90)
| Set the air conditioner temperature by pressing the move key or the increase key to modify this data.
| 100 (90) is the factory-set value, with a range set at 60-110.
|
5
| Setup Key
| 3
| -130 (140)
| Set the over-temperature alarm temperature value. Press the move key or increase key to modify this data.
| 130 (140) is the factory-set value, with a range set to 75-165.
|
Technical Specifications:
Ambient Temperature: -20~55℃
Relative humidity ≤ 90% (at 25℃)
Power Supply: AC 220±10% V
Display Value Compensation Range: 0~±20.0℃
Alarm Contact: 7A/250VAC
Sensor: Platinum Resistance (pt100) Φ3
Power Consumption: 8W
Measurement Range: -20 ~ ±200.0℃
Resolution: 0.1℃
Blower Contact: 16A/250VAC
Lead Wire Resistance: Ro ≤ 100Ω...
(Three-wire connection method) Accuracy: 0.5 grade
Dimensions: 260×200×70mm (Height×Width×Depth)
Hole Size: 230+1 x 180+1 mm (Height x Width)