1. Technical Basis

GB/T 12190-90 "Design Scheme for Shielding Effectiveness of High-Performance Shielding Rooms"

YDJ26-89 Provisional Technical Regulations for Grounding Design of Communication Bureau (Station), Standard of the People's Republic of China Ministry of Posts and Telecommunications

BMB3---1999 <Technical Requirements and Testing Methods for Electromagnetic Shielding Rooms Handling Classified Information>

GB 50222-95 <Code for Design of Fire Prevention in Interior Decoration of Buildings>

GB8702-88 <Regulations for Protection Against Electromagnetic Radiation>

GB9361-88 <Safety Requirements for Computer Workplaces>

GB6650-86 <Technical Conditions for Activity Floors in Computer Rooms>

2. Shielding Room Types:Welded steel plate electromagnetic shielding room structure.

The shielding room with a welded structure is assembled from different specifications of modular steel plates (plate thickness 2~3mm) welded together. It features a rectangular steel frame with varying load-bearing capacities designed to support the shielding shell at different locations, with its greatest strength lying in its rigidity, seismic resistance, stability, and reliability, surpassing other shielding rooms. Moreover, it offers significantly higher shielding efficiency.

3. Blocking Indices:

4. The shielding body is made of metal materials with an iron base, featuring 2mm thick steel plates. The ground utilizes steel plates of the same material and thickness of 3mm as the shielding layer.

Consider the shielding effectiveness of the shielding body material while also taking into account the overall mechanical properties of the electromagnetic shielding room. Design requirements include: steel plate unevenness ≤ 4mm/M2, shielding body verticality ≤ 10mm, and shielding body seismic resistance ≥ 8 levels.

5. Recommend electric lock for shielding door (with facial recognition and fingerprint password access)

6. Ventilation and Air Conditioning System: The ventilation system utilizes a shielded room-specific waveguide window, with insertion loss corresponding to the shielding room.

7. Air Conditioner Shielding Treatment: Shielding treatment for air conditioner power supply; shielding treatment for signal lines; shielding treatment for the three pipes of the air conditioner (gas pipe, liquid pipe, and drip pipe).

8. The power distribution system selects appropriately sized supply cables with suitable wire diameters and different capacity power filters based on the electrical load of each equipment.

9. Communication systems and signal interface devices for shielding rooms can be introduced into the room via dedicated fiber optic conduits, compatible with both multimode and single-mode optical fibers.

10. CAT5e cables exceed can be processed for shielding in the shielded interface box (multiple waveguide and copper tube treatments, supplemented with absorbing materials).

11. Telephone line entry into the shielding room can be equipped with a data signal filter.

12. Indoor Decoration

Interior decoration materials in the server room must be flame-retardant and waterproof. Common materials for walls and indoor ceilings include aluminum-plastic ceiling tiles, aluminum-plastic perforated ceilings, double-sided aluminum-plastic panels, and flame-retardant waterproof composite panels for finishes. The floor is made of static-free full steel modular flooring, with floor supports ranging from 110~300mm in height.

Secure the construction of the decorative layer's supporting framework with sufficient strength, which can be enhanced by using shielding bodies.

The entire interior should be aesthetically pleasing and spacious, with minimized empty space around openings. Enhanced workmanship precision is required, and all materials must be fire-resistant with a valid inspection report.