Product Features


EDHGQB-C Transformer Calibration Instrument

1. Calibrate the phase and percentage differences of current and voltage transformers.

2. Test the impedance of the secondary load of the current transformer.

3. Measure the admittance of the secondary load of the test voltage transformer.

4. Measure AC low current and AC low voltage.

5. With RS232 communication interface.


FY96 Current Transformer Load Box

Lightweight, attractive design, wide current range.

HJ-S10G3 Self-Rising Precision Voltage Transformer

10kV, 0.05 class voltage transformer is a high voltage grade, high accuracy transformer that can verify voltage transformers below 0.2 class, capable of handling a secondary load of 0.25VA at 100V secondary voltage.

EDKZX05-HII Dual-Tone Control Box

This series of control panels is designed for voltage regulation control of 0.5-5kVA test transformers. Working Principle: Adjusts the output voltage of the autotransformer to achieve regulation within the rated voltage range of the test transformer. Equipped with a high-voltage output voltage meter and a low-voltage output current meter, it allows for easy reading of test voltage values. The circuitry for overcurrent protection ensures reliable equipment protection, and the timing alarm circuit designed for convenience during testing. User feedback confirms its simple principle, compact structure, reliable operation, and ease of use, making it an ideal equipment for high-voltage testing.


Technical Specifications

1. Equipment operating environment

⑴. Temperature: 5℃ – 40℃; Relative Humidity: <80% (at 25℃); Altitude: <2500m

Power Frequency: 50Hz ± 0.5 Hz Power Voltage: 220V ± 5V

⑵. Measuring Range:

Coincident Fraction (%): 0.0001~200.0          Resolution: 0.0001

Orthogonal Component (Parts): 0.001 ~ 700.0  Resolution: 0.001

Impedance (Ω): 0.0001 - 20.0             Resolution: 0.0001

Impedance (ms): 0.0001~20.0          Resolution: 0.0001

③ Basic Tolerance:

Phase Quantity: ΔX = ±(X × 2% + Y × 2%) ± Dx (1st grade optional)

Orthogonal Component: ΔY = ±(X × 2% + Y × 2% × 34.48) (Option 1 available)

"X," "Y" — Instrument Display Values

"Dx, Dy" — Quantitative Error of the Instrument

Dx=2,Dy=5 

④. Dial Gauge: 1.5 grade (Grade 1 available)

2. Scope of Work:

Current: (1% - 149%) In (In = 5A)

(5%-149%)In    (In =1A)

② Voltage: (5% - 149%) Un (Un = 100V, 150V, 100V/)

          (5%-149%)Un    (Un =100V/3)

3. Workload:

⑴. Current: TO to TX < 0.12Ω, cosΦ = 1

⑵. Voltage: a to x < 0.25 VA (100V)

4. Polarization Error Indicator

Over 5% of rated working current (voltage), when the error exceeds 180%, polarity indication should be addressed.

Note: If the polarity indication is still not present beyond 10% above the rated working current (voltage), it indicates a fault. Do not increase the current (voltage) any further to prevent damaging the instrument.

5. Ratio Error Indication:

The transformer should indicate a ratio error when the rated working current (voltage) exceeds 5% and the error is more than 30% but less than 180%.

6. Insulation and Dielectric Strength Testing and Description:

Terminal TX (common terminal)

Power socket withstands 1.5kV, 1-minute voltage resistance

7. Key Features of Transformer Testing Instruments:

Utilizing a 320×240 pixel LCD array, it offers a wide viewing range with long-lasting backlighting for easy use.

⑵. Full Chinese operational interface, aesthetically pleasing.

③. The percentage gauge, percentage difference, and angle difference are displayed in extra-large font for easy observation by users.

Fully compliant with JJG314-2010 and JJG314-2010 requirements, with automatic sampling.

Automatically detect polarity errors and ratio errors.

⑥. The host software features virtual instrument open functionality.

Completely resolve S-class measurement issues.

Automatic range switching

⑼. Combining advanced unique circuitry and DSP technology, we have thoroughly resolved the instability issues with capacitive-inductive phase-shift circuits.

Power Consumption: < 15VA (without mini printer)

< 25VA (with micro printer)

Harmonic Suppression Ratio: > 40dB

Dimensions: 260mm (Length) × 350mm (Width) × 150mm (Height)

Weight: 6 Kg


Complete set of equipment