

价 格Negotiable
最小起订0 Piece库存0 Piece
72.5kV Dry Type Composite Wall-th
Negotiable
12kV Dry Type Composite Capacitiv
Negotiable
Cable-through fiber-glass impregn
Negotiable
40.5kV High Current Dry Type Comp
Negotiable
12kV High-Voltage Wall Penetratio
Negotiable
126kV Dry-Type Composite Capaciti
Negotiable
110kV Dry Type Composite Current
Negotiable
126kV Oil-impregnated Fiber Dry T
Negotiable
40.5kV Dry-type Composite Bushing
Negotiable
35kV Dry-Type Composite Current T
Negotiable
Product Introduction
This product is composed of main components such as the carrier fluid, capacitor core, outer sheath, skirt, flange, and end structure. A measuring tap is installed on the flange, which is opened for use during partial discharge and dielectric loss factor measurements. It should be reliably grounded during normal operation. The ends of the product are equipped with equipment clamps.
Reference Standards
·GB/T 4109-2008 "Insulating Sleeves for AC Voltage Above 1000V"
Product Model
![1610674782918728.png ]RCI]RY0}Z5M[XL[P({CNA5.png](https://www.pinsowang.com/file/upload/202303/04/093526969372.png)
Product Features
·Dry-type composite capacitive insulation, oil-free, gas-free, and porcelain-free
High dirt resistance level

Terms of Use:
·Environmental Temperature: -50℃ ~ +50℃
·Altitude: Design based on 1000m altitude; corrections are made according to GB 311 for altitudes exceeding 1000m.
·Foulness Grade: Outdoor IV/Indoor III (Special requirements, if any, to be noted)
Key Performance Indicators:
· Applicable rated voltage levels: 12kV, 24kV, 40.5kV, 72.5kV, 126kV, 252kV
· Rated Single-Phase Current: ≤2500A
Insulation level and electrical performance:
· Temperature Rise: Not exceeding 85K
Electrical Testing:
60 Hz power frequency withstand, partial discharge testing, dielectric loss, and capacitance
Operations and Maintenance:
Maintenance-free



Phone Consultation