Santec UPS Power Supply
Castle Series 3C3 Pro (20-200kVA)
The Castle 3C3 Pro is the latest generation replacement product for the classic Castle 3C3 series, utilizing full digital control technology and integrating significant achievements in contemporary power electronics and automatic control. It offers users a secure, reliable, stable, and environmentally friendly power guarantee for critical loads. While maintaining the high reliability and adaptability of the Castle 3C3 series UPS, the new Castle 3C3 Pro provides increased power, lower TCO, more reliable business protection, and easier maintenance and management.
| Key Performance Parameters | 3C3 Pro 20-200kVA | |||||||||
| Rated Power (kVA/kW) | 20/18, 30/27, 40/36, 60/54, 80/72, 100/90, 120/108, 160/144, 200/180 | |||||||||
| Online dual conversion mode system efficiency | As high as 94% | |||||||||
| ECO energy-saving mode system efficiency | As high as 98% | |||||||||
| Parallel operation capability | 4 units | |||||||||
| Battery cold start | 20-80K supported, 100-200K not supported | |||||||||
| Input Features | ||||||||||
| Rated Voltage | 380/400/415V | |||||||||
| Voltage Range | Line voltage: 340~478V | |||||||||
| 196~276V phase voltage | ||||||||||
| Frequency Range | 50/60 Hz, Range 42-72 Hz | |||||||||
| Input Current Harmonic Distortion | <2% Linear Load | |||||||||
| <5% Non-linear Load | ||||||||||
| Output Characteristics | ||||||||||
| Rated Voltage | 380/400/415V | |||||||||
| 3-line/4-line system | 3-line/4-line | |||||||||
| Rated Frequency | 50/60Hz | |||||||||
| Power Factor | 0.9 | |||||||||
| Voltage Stability | Steady State <1% | |||||||||
| Dynamic Response Characteristics | At load step from 0, <5% | |||||||||
| Total Harmonic Distortion (THD) Voltage | <2% linear load | |||||||||
| <5% Non-linear Load | ||||||||||
| Overload Capacity | 125% load, 10 mins | |||||||||
| 150% load, 1 min | ||||||||||
| Bypass characteristics | ||||||||||
| Rated Input Voltage | 3 x 380/400/415V | |||||||||
| Voltage Range | 359~438V line voltage | |||||||||
| 207~253V phase voltage | ||||||||||
| Battery Specifications | ||||||||||
| Battery Type | Lead-acid batteries, lithium-ion batteries | |||||||||
| Battery Voltage | 20-80 kVA: 336-432V, Default 384V | |||||||||
| 100-200kVA: 432-480V, default 480V | ||||||||||
| Charging method | Smart Battery Management | |||||||||
| Communication | ||||||||||
| Communication Slot | 2 Mini-slot slots | |||||||||
| Communication Interface | 3 building alarm inputs, 1 general dry contact output | |||||||||
| Certification and Certificates | ||||||||||
| Safety | IEC62040-1 | |||||||||
| EMC | IEC62040-2 | |||||||||
| Performance | IEC62040-3 | |||||||||
| Certificate | Taal / Energy-saving / CE /抗震 | |||||||||
| Appearance and Environmental Characteristics | ||||||||||
| Dimensions (WxDxH) mm | 20/30/40kVA: 350 x 805 x 800 | |||||||||
| 60/80kVA: 600 x 720 x 1200 | ||||||||||
| 100/120kVA: 600 x 796 x 1876 | ||||||||||
| 160/200kVA: 600 x 830 x 1876 | ||||||||||
| Weight (kg) | 20kVA | 30kVA | 40kVA | 60kVA | 80kVA | 100kVA | 120kVA | 160kVA | 200kVA | |
| 61.5 | 67 | 93 | 177 | 184 | 283 | 311 | 457 | 457 | ||
| Protection Grade | IP20 | |||||||||
| Storage temperature range | -15℃~55℃ | |||||||||
| Operating Temperature Range | 0℃~40℃ | |||||||||
| Work Environment Humidity | 5~95% Non-condensable | |||||||||
| Working Altitude | Altitude of 1000m or below, no derating required. | |||||||||
| Optional Accessories | NMC Cards | |||||||||
| Modbus RTU Card 744-98065 | ||||||||||
| Industrial Relay Card | ||||||||||