1500KW Cummins Generator Set Technical Specifications | |
Product Description | |
Cummins on-highway diesel generator sets are designed, manufactured, and tested to Cummins' global standards, offering clients a reliable and integrated power generation system with superior performance under normal, standby, and continuous operation conditions. ➊ CompliantISO 8528-2005 and GB/T 2820-2009 Standard for "AC Generating Sets Driven by Reciprocating Internal Combustion Engines" ➋ Design and manufacturing of the generators have both passedISO 9001 or ISO 9002 certification. ➌ Cummins offers1-year or 1000 operating hours warranty, covering full warranty for the generator set, including the engine, generator, and control system. ➍ A nationwide professional service network serving customers24/7 after-sales service and technical support. | |
Performance Features | |
■ Lubrication System: All moving parts are under forced lubrication; gear pumps supply pressurized lubricating oil to lubricate and cool the piston bearings. | |
Environmental Requirements | |
Altitude(m):≤1000 Fuel Standard:0# Diesel Fuel Atmospheric Pressure(kPa):≥89.9 Engine Oil Standards:CF/15W-40 Intake Temperature(℃):≤40 | Water QualitypH Level: 6.5-8 Relative Humidity:≤60% Mold Level on Surface≤ GB/T2423.16/2 grade Seismic Resistance: Horizontal Acceleration0.2g vertical acceleration, 0.1g |
Generator set specifications | |
Model Type: Open Shelf Engine Model:C1500GF Standby Power(KW):1600 Standard Power(KW):1500 Engine assembly dimensions(mm):6200x2380x2500 Engineered Weight(kg):14800 RPM(r/min):1500 Fuel Consumptiong/kw.h):205 Frequency(HZ):50 | Transient Voltage Regulation Ratio:≤-15%/+20% Steady-state voltage regulation:≤±1% Voltage Stabilization Time:≤3sec Voltage fluctuation rate:≤0.5% Voltage waveform distortion:≤8% Steady-state frequency adjustment rate:≤5% Transient Frequency Adjustment Rate≤-10%/+12% Stable Frequency Time:3sec Frequency volatility:≤1.5% |
Engine specifications | |
Diesel Engine Brand:Cummins/Cummins Manufacturer:Chongqing Cummins Engine Co., Ltd. (CCEC) Diesel Engine Model:KTA50-G16A Standby Power(KW):1760 Number of cylindersArrangement: 16-cylinder V-type Compression Ratio:13.9:1 Bore diameter* Travel (mm): 159*159 DisplacementL):50.3 Oil Pressurepsi):50~70 Oil Temperature℃):≤121 | Oil capacity(L):204 Cooling Water Capacity(L):477 Fuel System:PT Pump Direct Injection Cooling Method: Closed-loop Water Cooling Startup Method:DC24V Electric Start Speed Control: Electronic Speed Control Inlet Method: Turbocharged, Intercooled Type: Four-stroke60° Constant Load Steady-State Fluctuation Rate±0.25% Power Deviation:≦±5% |
Generator specifications | |
Generator Brand:Stamford/Stanford Manufacturer: Cummins Generator Technologies (China) Co., Ltd. Generator Model:S7L1D-F41 Rated Capacity:1500KW Voltage:400V/230V Form: Brushless, Single-Bearing, Rotating Magnetic Field Excitation System: Self-excitation, Automatic Voltage Regulation Winding structure:2/3 pitch Three-phase four-wire | Insulation Grade:H Grade Power Factor:COSΦ = 0.8 lagging Telephone Interference Factor:TIF:<50 Wiring:Y-connection Telephone Harmonic Coefficient:THF:<2% Protection Level:IP23 Radio Frequency Interference (RFI): CompliantBS800 and VDE Class G, N Meets Standards:GB755, BS5000 Part 3, VDE0530, NEMA MG1-22, IEC-34, GSA C22-100, AS1359 |
Standard Configuration | |
Engine Components: Engine, Diesel Filter, Air Filter, Oil Filter, Charger, Starter Motor. Generator section: Generators, circuit breakers. Control System:LCD liquid crystal display controller, electronic speed controller. Other Components: Water Tank Radiator, Steel Base, Vibration Dampers. Attachment section: muffler, battery, battery cable, engine oil, vibration dampener. | |
Execution Standards | |
Military Specifications GJB 5785-2006 National Standards GB/T 2820-2002 Communication Standards YD/T 502-2007 | Industry Standards JB/T 10303-2001 Environmental CertificationNoise and Vibration Class A / Exhaust Emission Class A Teral Quality Certification YD/T502-2007* |