What is the function of the high and low-pressure switches on a 10-ton bipolar reverse osmosis equipment?_Engineering Case Studies Co., Ltd._What is the function of the high and low-pressure switches on a 10-ton bipolar reverse osmosis equipment?,Xi'an Kangnuo Environmental Protection Technology Co., Ltd._Xi'an Kangnuo Environmental Protection Technology Co., Ltd._Zhongshang 114 Industry Resources Network
Xi'an Kangnuo Environmental Protection Technology Co., Ltd.

Reverse Osmosis Equipment | Water Purification Equipment | Ultrafiltration Equipment | Pure Water Equipment | Smart Water Management | Water Supply Equipment | Disinfection Equipment | Soft Water Equipment | Sewage Treatment Equipment | Water Treatment Consumables

Consultation Hotline
13679111997  13679111997
 

Company Information

Location:Shaanxi/Xi'an

会员级别:数字营销4

身份认证:   

我的勋章:  通过中商114认证 [诚信档案]

Business Card

  • 公司名称Xi'an Kangnuo Environmental Protection Technology Co., Ltd.
  • 联 系 人常经理 (先生)
  • 公司电话13679111997
  • 手机号码13679111997
  • Company Address4/F, B Block, 705 Room, Bao Lin Science & Technology Industrial Park, Middle Section of Huo Gu Road, Bao Lin District, Xi'an, Shaanxi Province
home > Engineering Case Studies Co., Ltd. > What is the function of the high and low-pressure switches on a 10-ton bipolar reverse osmosis equipment?
Engineering Case Studies Co., Ltd.
What is the function of the high and low-pressure switches on a 10-ton bipolar reverse osmosis equipment?
Publish Time:2022-06-16        View Count:61        Return to List

What is the function of high and low voltage switches on a 10-ton bipolar reverse osmosis equipment?

Reverse osmosis equipment with high/low pressure protection is designed to prevent the RO high-pressure pump from running empty or operating under excessive high/low pressure conditions.

High-pressure switches are used for high-voltage protection. As the usage time of reverse osmosis equipment increases, the RO membrane can become polluted and clogged, leading to an increase in the pressure of the imported natural membrane. When the pressure reaches a certain level, a high-pressure switch is required to protect the water treatment equipment from damage. Once the pressure reaches the preset value of the pressure switch, the reverse osmosis equipment will be forced to shut down.

For low-pressure switchgear, when the pressure inside the incoming water pipe is low, the RO reverse osmosis membrane cannot operate normally, and wastewater will be discharged continuously. Therefore, when the incoming water pressure does not meet the operational requirements, the circuit will be disconnected, and the reverse osmosis equipment will cease operation. Once the pressure inside the incoming water pipe meets the operational requirements, the system will resume operation.

How to Adjust the Pressure Switch of a Water Treatment Reverse Osmosis System?

The low-pressure switch features two adjustable screws: one for the base pressure regulation, typically ranging from 0-6bar, and another for the differential pressure regulation, usually from 0-2bar, which can be adjusted according to the tool.

Common low-pressure switches often have two types of jumps: one is due to significant fluctuations in the raw water pressure, and the other occurs when the reference pressure is close to the raw water pressure value, with a smaller hysteresis pressure.

Original Water Pressure Fluctuation Solution.

Exhaust Pretreatment Equipment. Increasing the opening of the raw water pump outlet valve to achieve a relatively higher raw water pressure, which is less prone to fluctuations.

Xiaohui Differential Pressure Solution

Firstly, observe the pressure of the reverse osmosis equipment during normal operation, adjusting the base pressure slightly below 2.5 bar, then set the base pressure to 2 bar.

2. Set the pressure value for the low-pressure trip, for instance, the pressure switch starts to jump when the raw water pressure is below 1.5 bar; then adjust the back pressure difference to 0.5 bar.

3. Although adjustments have been made, the precision varies. Therefore, adjustments should be made based on the actual pressure conditions before meeting internal requirements. For instance, absorption occurs at 2bar pressure, while skipping happens at 1.5bar pressure (at this point, pressure can be regulated by adjusting the high-pressure pump valve or the original pump outlet valve).

4. To achieve a greater pressure differential, you can also adjust the differential pressure to 0.8-1.0 bar. This way, the system can absorb at 2 bar and bypass when the pressure falls below 1 bar.