- AllProduct Category
-
Domestic Explosion-Proof Certification
Explosion-Proof 3C Certification
Explosion-proof Electrical Inspection
Coal Mine Safety Certification
ATEX & IECEx Certification
Ex-proof Qualification Certificate
Explosion-proof Construction Renovation


详情描述
Shenzhen Zhongnuo Testing Technology Co., Ltd. specializes in the calibration, certification, and metrological services for gas detectors, flammable gas detectors, and harmful gas detection instruments for various locations. We offer nationwide services, addressing electrical safety and explosion-proof fire prevention issues for clients, and contribute to safe production.
What are the contents of the report for calibration of combustible gas detectors?
The verification results should be reflected on the verification certificate or report, and the verification proof or report must include the following information.
① Calibration Certificate or Calibration Report
② Laboratory Name and Address
③ Calibration Location (if not calibrated in the laboratory)
④ Standing proof or report (e.g., numbered), with indication of each page and page number;
5. Shipper's name and address
⑥ Describe and clearly define the target school.
Calibration Date and Receipt Date
⑧ Technical specifications for calibration base, including name and code;
Description of the traceability and validity of the measurement standards used in our calibration.
⑩ Description of Calibration Environment
11. Calibration Results and Measurement Uncertainty Statement
12. Signature, title, or equivalent emblem of the issuer of the calibration certificate or report, and the issuance date;
13. Calibration results are only applicable to the calibration object.
14. No part of the certificate or report may be copied without written approval from the laboratory.
Reproofreading interval
Instrument recalibration is typically every 1 year, determined by the submitting unit based on actual usage. During the secondary calibration process, if there are doubts about the instrument's test data, or if the main components of the instrument are replaced, as well as after repairs, a recalibration is required.
Regulatory contents and methods for periodic testing of flammable gas detectors
Annually, we conduct annual inspections on the sensors of commercial and industrial alarm systems, primarily checking for the accuracy, repeatability, drift, and response time of the alarms to ensure they meet standards. Additionally, we verify the appropriateness of the alarm installation location and whether it is subject to interference from other equipment.
The detection principle of the instruments mainly includes catalytic combustion, infrared absorption, and thermal conductivity types. The sampling methods include diffusion and aspiration. The instruments are primarily composed of detection elements, amplification circuits, alarm systems, and displays, used for monitoring the concentration of combustible gases in the environment.
Method of Verification
Appearance and structure
Inspect and feel according to the requirements of Section 4.1
Logos and Branding
Observe as per the requirements of Section 4.2.
Power-on Inspection
Inspect visually and by touch according to the requirements of 4.3 to check the alarm function and alarm action values as per 5.3.4.
Introduce a standard gas substance with a concentration exceeding the alarm set point, causing the instrument to trigger an alarm. Observe whether the instrument's sound and light alarm functions properly, and record the reading at the time of the alarm. Repeat the measurement three times, and the arithmetic mean of the three readings is the instrument's alarm trigger value.
Shenzhen Zhongnuo Inspection Technology Co., Ltd. is a third-party institution specializing in electrical safety, electrical explosion-proofing, gas detectors, and toxic gas alarm instruments for regular inspections, metrological measurements, and calibrations. We are qualified to address fire and explosion prevention issues for our clients.