Lng Storage Tank, Lng Low-Temperature Storage Tank, Lng Liquefied Natural Gas Storage Tank, Brand: He Guo_SupplyPro Co., Ltd._Shandong Zhongjie Special Equipment Co., Ltd. 
在线客服 在线客服邀请中...
关闭

您好,现在客服正邀请与您通话,请留下您的联系方式,客服将尽快与您取得联系。

 点击提交代表您同意《服务条款》《隐私政策》
Shandong Zhongjie Special Equipment Co., Ltd.

Zhongjie Special Tank Co. specializes in the installation services of LNG tan...

Consultation Hotline
15253010956  18769007684

News Center Co., Ltd.

Product Categories
  • No Category

Contact Information
  • Contact person:于秋波
  • Telephone:15253010956
  • 邮件:931369632@qq.com
  • Mobile:18769007684

Home > SupplyPro Co., Ltd. > Lng Storage Tank, Lng Low-Temperature Storage Tank, Lng Liquefied Natural Gas Storage Tank, Brand: He Guo
Lng Storage Tank, Lng Low-Temperature Storage Tank, Lng Liquefied Natural Gas Storage Tank, Brand: He Guo
品牌: Zhong Jie
Inventory Quantity: 9999
Working Voltage: 380V
Effective Water Capacity: Please inquire in detail.
单价: 1.00/Tai
最小起订Quantity: 1 Tai
供货总Quantity: 9999 Tai
有效期至: 长期有效
最后更新: 2025-05-29 08:43
 
详细Info

Product Description


Brand Huoguo Group Model CFW-100/0.8

Material: Stainless Steel | Diameter: 3400mm

Application Range: -162℃; Volume: 100,000L

Heat Exchange Area - See drawing sq. m Ambient Temperature - See drawing °C

Wall Thickness: 10/12mm, Dimensions: 3424*16442mm

Origin: Shandong Heze

    


60-cubic-meter LNG Tank Price | Manufacturer Supplies 30-cubic-meter and 60-cubic-meter Tanks


3. LNG Tank Fault Inspection and Treatment 3.1 Daily Inspection


3.1.1  Are the level gauges and pressure gauges functioning properly?


3.1.2 Are the shut-off valves, regulating valves, and safety valves in normal working condition?


3.1.3 Tank, pipeline, and valve leaks inspection.


3.2 Regular inspections


3.2.1 Pressure gauges should be calibrated annually and accompanied by a test certificate with a lead seal.


3.2.2 The safety valve should be calibrated annually and sealed with lead.


3.2.3   Low-temperature liquids should be analyzed every three to six months as required for operation.


3.3 Fault Handling


Fault occurred


Original Cause


Processing Measures


1. Abnormal inner tube pressure


(Raise or Lower)


A Pressure Gauge Distortion


B Tank Vacuum Reduction


Operation error on C valve


A Pressure Gauge


B Weight Vacuum Picked


C conforms to manual operation requirements


Level gauge distortion


Improper operation of the A level gauge valve


The B level gauge is damaged.


Reoperate as per requirements


B Replace with new level gauge


3 External tank frosting


A vacuum failure


B-laminate leakage


C Color Pearl Sand Sink


A re-evacuate the vacuum


B pressure test and leak detection, then evacuate air


Please re-install pearl sand in the C-balance sandwich and then evacuate the vacuum.


Please note:


If the user needs to evacuate or re-install pearlescent sand in the sandwich, they must first empty the inner cylinder liquid and wait until the inner cylinder returns to room temperature before proceeding.


2. Should users encounter issues that are difficult to handle, they may contact our after-sales service department promptly. Our company offers a three-package quality guarantee for our products. We also provide repair services for products beyond the warranty period and for non-company products.


4. Cautionary Notes


4.1 The vacuum valve is sealed before the product is shipped out. Upon delivery to the user's site, the user must ensure to protect all pipeline valves during installation, particularly the vacuum valve, and strictly prohibit any collision or opening of the vacuum valve.


4.2 Do not empty the liquid in the storage tank unless it is for an extended period, as this can cause the inner cylinder to overheat, necessitating additional cooling when refilling, leading to unnecessary losses.


4.3 Low-temperature liquid storage tanks are used for storing liquid nitrogen, liquid oxygen, and liquid argon. However, when switching to another liquid, the original liquid must be completely emptied and purged before refilling with the new liquid.


Note:


1. The measuring full valve opens when the liquid is almost full, closes when liquid starts to flow, and stops the inflow. When filling for the first time, it should be filled from the top first, followed by the bottom.


2. Open during waste liquid discharge.


3. Release the vent valve when the container pressure is too high.


4. The container automatically opens when over-pressurized. Normally, only one is used. If the working one fails, the other is immediately activated to ensure the safe operation of the storage tank. The damaged safety valve is then repaired and inspected, and upon passing, it is promptly reinstalled.


5. The inner cylinder automatically starts upon opening the boost valve when the pressure boost is required.


6. The level gauge is usually turned off during normal operation.


7. Burst upon overpressure; must be replaced immediately if bursting occurs.


 









 

Natural Gas Storage Tank Price - 100 Cubic Horizontal LNG Storage Tank Direct from Manufacturer - Price Discount - High Vacuum Level


Product Description


Brand Hekou Group Model CFW-60/0.8

Material: Stainless Steel, Diameter: 2916mm

Application Range    -162℃    Volume    60000L

Heat Exchange Area  See Drawing sqm  Ambient Temperature  See Drawing °C

Wall Thickness: 8mm, Dimensions: φ2916*14929mm

Origin: Shandong Heze

    




60-cubic-meter LNG Storage Tank, Horizontal LNG Tank, Manufacturer Specializing in 60-cubic-meter Liquefied Natural Gas Tanks Supply


LNG tanks are atmospheric pressure, low-temperature, large capacity storage vessels, typically with a flat bottom and double-walled cylindrical design. The inner cylinder is usually made of 9% nickel alloy steel, but can also be constructed from all aluminum, stainless steel foil, or pre-stressed concrete. The outer wall is made of carbon steel or pre-stressed concrete. The suspended insulating support platform at the top of the wall is aluminum, while the tank roof is made of carbon steel or concrete. The main insulating materials inside the LNG tank include expanded perlite, elastic glass fiber felt, and foam glass bricks.


LNG Tank Characteristics Requirements


Low-temperature resistance


The boiling point of liquefied natural gas at atmospheric pressure is -162°C. Therefore, LNG storage tanks must have excellent low-temperature resistance and superior insulation properties.


(2) High safety requirements


Due to the storage of low-temperature liquids inside the tank, in the event of an accident, the refrigerated liquid would volatilize in large quantities, with the vaporization amount being approximately 625 times that of the refrigerated state, forming an explosive mixture in the atmosphere. Therefore, it is required that the tank be constructed with a double-walled structure and utilize the containment concept. In the event of a leak in the first layer of the tank, the second layer can completely contain the leaked liquid and the evaporated gas, ensuring storage safety.


(3) Special material.


The inner tank must be capable of withstanding low temperatures and is made of austenitic stainless steel, while the outer cylinder is constructed from Q345R ordinary low-carbon alloy steel plate.


(4) Insulation measures are stringent.


Due to the maximum temperature difference between inside and outside the tank reaching up to 200℃, the tank must have excellent insulation properties to maintain an internal temperature of -160℃. High-performance insulation materials should be filled between the inner and outer shells. The insulation material at the bottom of the tank must also have sufficient load-bearing capacity. (5) Good seismic performance


General building seismic requirements are to crack under specified earthquake loads but not collapse. To ensure the safety of storage tanks under unexpected loads, they must possess excellent seismic performance. Ensure that the tank body remains undamaged under the given seismic intensity. (6) Strict construction requirements


The tank welds must undergo 100% magnetic particle testing (MT) and 100% vacuum leak testing (VBT). Strict selection of insulation materials is required, and the prescribed procedures must be followed during construction.


Huzhou Boiler Factory Co., Ltd. is a key enterprise designated by the China National Quality Supervision, Inspection and Quarantine Administration for the production of boiler pressure vessels. It is an affiliate member of the China Industrial Boiler Industry Association and a member of the China Association of Heating, Ventilating, Air Conditioning and Drainage. The company holds B-grade boiler manufacturing资质 (No. TS2110587-2011), third-class pressure vessel manufacturing资质 (No. TS2210916-2013), and design qualifications (No. TS1237085-2011), and has passed the ISO9001 international quality management system certification.


Heze Boiler Factory Co., Ltd. Main Products:


Chemical Storage Tanks (liquefied gas tanks, liquefied petroleum gas tanks, liquid ammonia tanks, propane tanks, propylene tanks, isobutane tanks, methyl chloride tanks, etc.); Non-standard Pressure Vessels (towers, heat exchangers, autoclaves, reaction vessels, stainless steel containers, etc.)


Refrigeration Auxiliary Equipment (evaporative coolers, ammonia storage tanks, condensate drums, circulating drums, oil separators, separators, condensers, intermediate coolers, siphon tanks, economizers, etc.)


Boiler equipment (Steam boilers, hot water boilers, thermal oil boilers, oil-gas boilers, waste heat boilers, etc.)


Low-temperature Storage Tanks (Liquid Oxygen Tanks, Liquid Oxygen Vessels, Liquid Nitrogen Tanks, Liquid Nitrogen Vessels, Liquid Argon Tanks, Carbon Dioxide Tanks, LNG Tanks, Liquefied Natural Gas Tanks)


 





 

60-cubic-meter LNG Tank, Horizontal LNG Tank, Professional Manufacturer of Liquefied Natural Gas Storage Tanks





Heze Boiler Liquefied Natural Gas Storage Tank Gas Steam Boiler - Liquefied Natural Gas Tank Brand - How Much for a High-Quality Liquefied Natural Gas Tank - High-Quality Liquefied Natural Gas Tank Supplier
询价单
 Click submit means you agree to《Service terms》《Privacy policy》

18769007684