公司主营:Leqing Yijin Electronics Co., Ltd. is a professional manufacturer of low-voltage electrical appliances, an integrated economic entity encompassing research and development, manufacturing, sales, and services.
13868370306




企业资质
The Differences Between Photovoltaic Automatic Reclosing Switches and Self-restoring Overvoltage Protectors
2024-02-24
The XY47-63 automatic reclosing switch is a miniature circuit breaker designed for circuits with rated working voltage of 50Hz up to 400V and rated working current of 80A. It can be used for remote automatic closing, opening control, or automatic signal control.
The circuit breaker provides overload and short-circuit protection, and can be paired with a voltage-loss release to enable power-off activation and automatic shutdown upon power restoration. It is currently widely used in photovoltaic grid-connected AC distribution boxes, as well as in areas where access is difficult, where maintenance personnel cannot arrive in time, in unattended environments, and in situations where a high level of power supply continuity is required.
2. Self-Recover Overvoltage Protector: The self-recoverable overvoltage protector is suitable for users or loads with single-phase AC voltage of 220V and a frequency of 50Hz, and rated working current of 60A or less. It provides protection for single-phase electrical equipment against under-voltage in single-phase lines caused by neutral line faults. Mainly used for protecting the incoming lines of residential household cabinets or distribution lines for single-phase electrical equipment that requires protection.
Usage Instructions:
When a single-phase line experiences overvoltage or undervoltage, the line will automatically disconnect, and the voltage of the single-phase line will return to normal. After a delay of 1-2 minutes, the line will automatically reset and reconnect, without the need for manual shutdown operations.
2. When transient or transient overvoltage conditions occur on the line, measured in seconds, the protector does not activate.
3. The protector will not connect the circuit when the line voltage is unstable due to faults like incorrect contact, or during sudden power outages or power restoration.
4. When the line voltage fails, the protector itself will not be damaged.
5. The protector features an anti-time delay action, with an operating time ≤ 1s.
6. Voltage Protection Range: Below 40A - 0 ~ 450V, 50/60A - 0 ~ 600V.
7. Impulse Withstand Voltage: 4kV (compliant with III category electrical safety standards).
8. The protector panel features bi-color indicator lights to denote operational status, with green indicating normal line voltage and red signaling positive-negative line voltage or delay.
9. Modular design with guide rail installation.
10. Wire Connection Specifications: Insulated wires with a cross-sectional area of 25mm2 and below.
11. Panel Width: 1st Generation 45mm, 2nd Generation 45mm: 36mm = 2 pdz 47 (easier for installation and use with limited-sized distribution boxes)
Technical Specifications:
Working Voltage: AC 220V, Frequency 50Hz
2. Product Specifications: 20A, 32A, 40A, 50A, and 60A, in three sizes. Load Power: 4.4kVA, 6.6kVA, 8.8kVA, 11kVA, and 13.2kVA.
4. Overvoltage trip setting: AC270 5V
5. Overvoltage Recovery Value: AC255 5V
6. Under-voltage trip setting: AC170 5V
7. Undervoltage Recovery Value: AC 185V, 5V
8. Power transmission delay after blackout: 30±10 seconds.
9. Action latency: ≤1 second
Self-Consumption Power: ≤2W
Electrical and mechanical lifespan: ≥ 100,000 cycles.
吕学学 (Mr.)
13868370306
13868370306
Zhejiang Province, Wenzhou City, Leqing City, Beibaixiang Town, Xiaofang Industrial Area
b2b.china9.net © Zhongshang 114 Hebei Network Technology Co., Ltd.Address: Room 6009, Oriental New World Center, No.118 East Zhongshan Road, Qiaoxi District, Shijiazhuang City, Hebei ProvincePlatform Service Hotline: 4006299930