Product Name: Constant Pressure Water Supply Unit
Operating Principle:
Upon initial operation of the pressure-regulated water supply unit, the water supply pump is first activated to fill the water chamber within the system and the pressure vessel. Once the system is full, excess water is forced into the capsule. As the water volume continuously increases, the volume of the water chamber expands, compressing the air chamber, and the pressure inside the tank also rises. When the pressure reaches the designed level, the water supply pump is shut off by the pressure controller. When the water inside the system expands due to heating, causing the system pressure to exceed the design pressure, the excess water is discharged through a safety valve into the water supply tank for recirculation.,When water in the system contracts due to leakage or temperature drop, it is continuously pressed into the pipeline to compensate for pressure drop losses. When the system pressure drops to the minimum pressure allowed by design, the pressure controller restarts the booster pump to replenish water into the pipeline and air tank, repeating this cycle.
Product Features:
The tank is internally fitted with a non-toxic rubber bladder, ensuring water and air do not come into contact, thereby guaranteeing water quality remains uncontaminated and the tank is not corroded.
2. Gas and water separation, excellent sealing performance; one-time inflation for long-term use.
3. Features include voltage stabilization, continuous water replenishment, expansion, and automatic pressure relief upon overpressure. It operates with automatic control, is easy to use, and offers reliable performance.
4. Compact footprint, flexible configuration, complete unit factory shipment, quick assembly, easy operation and maintenance.
5. High-level water tanks and water towers replacing domestic, fire, heating, and air conditioning systems.
Environmental and working conditions
Ambient Temperature:0℃~40℃
Relative Humidity: <95% moisture-free
Shake Motion: <0.5g Vibration Frequency10Hz to 150Hz, vibration acceleration shall not exceed 5 m/s²
Tilt Angle: <5 degrees Power Frequency:50Hz
Power Voltage:380V±10%
YDNZP Series Specifications Sheet
Item Number | Name | Unit | ø600 | ø800 | ø1000 | ø1200 | ø1400 |
1 | Design Pressure | MPa | 0.6 /1.0 /1.6 | ||||
2 | Full Capacity | m3 | 0.35 | 0.82 | 1.38 | 2.45 | 3.44 |
3 | Adjustable Volume | m3 | 0.125 | 0.28 | 0.50 | 0.83 | 1.16 |
4 | Operating Temperature | ℃ | 120℃Below | ||||
5 | Air Conditioning Cooling Area | 10000 | 18000 | 25000 | 35000 | 48000 | |
6 | Air Conditioner Heating Coverage Area | M2 | 20000 | 40000 | 60000 | 80000 | 120000 |
7 | Total System Volume | M2 | 4-8 | 10-18 | 18-30 | 30-50 | 50-70 |
Note:Flow rate and head of the water pump are based on customer's configuration requirements