Fire Control Room Equipment Arrangement Requirements_News Center Co., Ltd._Fire Control Room Equipment Arrangement Requirements,Lan Yuan Architectural Design & Planning Co., Ltd. - Shenyang Branch_Lan Yuan Architectural Design & Planning Co., Ltd. - Shenyang Branch_Zhongshang 114 Industry Resources Network
Lan Yuan Architectural Design & Planning Co., Ltd. - Shenyang Branch

A specialized technical consulting firm engaged in fire protection drawing design, with a professional design team and robust technical strength.

Service Hotline
13066770119


Company Information

Location:Liaoning/Shenyang

会员级别:数字营销2

身份认证:    

我的勋章:  通过中商114认证

Business Card

  • 公司名称Lan Yuan Architectural Design & Planning Co., Ltd. - Shenyang Branch
  • 联 系 人张经理 (先生)
  • 公司电话13066770119
  • 手机号码13066770119
  • Company AddressNo. 11-11 Shiji Road, Hunnan District, Shenyang City, Liaoning Province (2-282)

News Category
  • No Category

Contact Information
  • Contact person:张经理
  • Telephone:13066770119
Home > News Center Co., Ltd. > Fire Control Room Equipment Arrangement Requirements
News Center Co., Ltd.
Fire Control Room Equipment Arrangement Requirements
Publish Time:2024-09-05        View Count:23        Return to List

The fire control room is a specialized location equipped with automatic fire alarm control devices and fire control equipment, designed to receive, display, and process fire alarm signals, and control related fire protection facilities. Fire control rooms should be established within the protected areas of fire automatic alarm systems with fire联动 functionality.

The operating distance in front of the equipment panel should not be less than 1.5 meters when arranged in a single row; for double-row arrangement, it should not be less than 2 meters.

2. On the side where the staff regularly work, the distance between the equipment panel and the wall should not be less than 3 meters.

The maintenance distance behind the equipment panel should not be less than 1 meter.

When the arrangement length of the equipment faceplate exceeds 4 meters, both ends should be equipped with a passage that is at least 1 meter wide.

In the fire control room shared with other low-voltage electrical systems in buildings, fire equipment should be centrally located and should have a clear separation from other equipment.